| 2006-06-23 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW, ELECTRICAL PLANS HAVE |
| | BEEN VOIDED. PLEASE SEE NOTES BELOW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS. PLEASE SEE |
| | MISSING THE PRINTED NAME OF ENGINEER AS |
| | REQUIRED PER FAC 61G15-23.002. |
| | PLEASE SEE ABOVE AND 61G1-16.004. |
| | PLEASE ALSO SEE ADDRESSING AND SUITE # |
| | ON PLANS ARE NOT CORRECT. |
| | PLEASE SEE FRONT COVER SHEET INDICATES |
| | 600 S ROSEMARY WHEN SITE IS LOCATED AT |
| | 700 S. ROSEMARY. PLEASE BE SURE ALL |
| | TITLE BLOCKS ARE REVISED. |
| | PLEASE ALSO SEE THE SUITE # OF B-17 IS |
| | NOT CURRENT. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER. |
| | |
| | 2) NOTE; PLEASE SEE PLANS NOTES MENTIONS |
| | THE PLANS ARE DESIGNED UNDER THE 2004 |
| | FBC, HOWEVER PLEASE SEE FBC 2004 CHAPTER |
| | 13 FOR NEW REQUIREMENTS WHICH COULD BE |
| | LOCATED ON PLANS. |
| | PLEASE PROVIDE AUTOMATED LIGHTING |
| | CONTROLS AS REQUIRED PER |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | PLEASE LIST SCHEDULING, OVER-RIDE |
| | LOCATIONS AS REQUIRED ALONG WITH THE |
| | TIME LIMITS ON THE OVER-RIDE DEVICES |
| | USED IN CONJUNCTION WITH THE NEW |
| | LIGHTING CONTROL SYSTEM. |
| | PLEASE SEE 13-415.1.AB.1 AND |
| | 13-415.2.ABC.1 FOR MIN CALCULATIONS |
| | REQUIRED FOR ALL LIGHTING IN AREAS AND |
| | THE MAX ALLOWED LIGHTING DENSITIES, |
| | PLEASE SEE TABLES AND DETAIL WHICH |
| | OPTION IS BEING USED. |
| | PLEASE SEE ALL OF 13-413/415 |
| | |
| | 3) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | ** PLEASE SEE THE RATING OF 25K IS SHOWN |
| | FOR THE 120/208V "LV" PANEL, BUT NOT FOR |
| | "HV" OR THE NEW MAIN DISCONNECT ON THE |
| | LOAD SIDE OF THE METER IN MAIN |
| | ELECTRICAL ROOM. |
| | |
| | 4) NOTE: PLEASE CORRELATE AHU LOADS AS |
| | PANEL SCHEDULE INDICATES 12,135VA, YET |
| | LOAD CALCULATIONS INDICATE 10KW? |
| | 215.5 |
| | |
| | ** PLEASE KNOW, IF PLANS COME BACK WITH |
| | OUT ANY OTHER COMMENTS FROM ANY TRADE(S) |
| | THEN A "RESUB" FEE WILL NOT BE REQUIRED. |
| | HOWEVER IF THERE ARE ANY COMMENTS, THEN |
| | THE RESUB FEE WILL BE ASSESSED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |