| 2006-05-24 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} HAVING ADDED A DISCONNECTING MEANS | | | AND A METER, PLEASE SHOW COMPLIANCE WITH | | | 230.71, NUMBER OF DICONNECTS, A RISER | | | WILL SUFFICE. | | | | | | 2} NOTE #7, SHEET E-2, INDICATESA 45 | | | KVA TRANSFORMER, THE SCHEMATIC /RISER, | | | SHOWS 112.5 KVA TRANSFORMER, PLEASE | | | CORRELATE. | | | | | | 3} NOTE #3 INDICATES A 200 AMP | | | DISCONNECT WITH 200 AMP FUSES. THE RISER | | | SHOWS A 400 AMP DISCONNECT WITH 400 AMP | | | FUSES (400/400) AND ALSO HAS 200 AMPS | | | WRITTEN ON IT. PLEASE CORRECT. | | | | | | 4} PLEASE INDICATE CIRCUIT NUMBERS ON | | | THE EXIT AND EMERGENCY LIGHTS PER | | | 700.12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|