| Notes |
| Date |
Text |
| 2006-09-28 00:00:00 | ----------------DENIED------------------ | | | 1. PAGE M2 QUADRANT 2B: MISSING FIRE | | | DAMPER ON 8" ROUND DUCT FROM TO 05 VAV | | | IN 'RECEPTION' TO 'OFFICE' 250 CFM DROP. | | | | | | 2. PAGE M10 DETAIL #2: PLEASE INDICATE | | | OF WHAT MATERIAL THE ROOF DUCT STANDS | | | ARE TO BE CONSTRUCTED, AS WELL AS DETAIL | | | FOR FASTENING STANDS TO ROOF IN ORDER TO | | | MEET WIND-LOAD REQUIREMENTS. | | | | | | 3. PAGE M10 DETAIL #1B: ALL UL 155 | | | LISTED FIRE DAMPERS MUST BE INSTALLED | | | ACCORDING TO MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS. PROVIDE THEM EITHER ON THE | | | PLAN OR SEPERATELY. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|