| Plan Review Notes For Permit 06050845 |
| Permit Number |
06050845 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-24 00:00:00 | PLAN DENIED | | | 1) MISSING FIRE DAMPER IN CONFERENCE | | | ROOM PAGE M-1. | | | 2) MISSING FIRE DAMPER IN JURY ROOM PAGE | | | M-2 | | | 3) PLEASE PROVIDE ON THE PLANS ALL DUCT | | | AND GRILL SIZE FOR QUADRANT 4-B PAGE M-4 | | | 4) PLEASE REFER TO SECTION 606.4.1 | | | SUPREVISON 2004 FBC(M) | | | 5) PLEASE REFER TO SECTION 307.2.3 | | | AUXILIARY AND SECONDARY DRAIN SYSTEM. | | | 2004 FBC(M). | | | 6) PLEASE REFER TO SECTION 307.2.1 | | | CONDENSATE DISPOSIAL 2004 FBC(M). | | | 7) PLEASE PROVIDE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS ON NOTE # 2 | | | PAGE M-10 | | | 8) PLEASE PROVIDE A DETAIL FOR A/C CURB | | | TIE DOWN TO ROOF ON PLANS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|