| Date |
Text |
| 2006-06-10 00:00:00 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THIS WAS ORIGINALLY |
| | SUBMITTED UNDER THE 2001 FBC AND ONLY AS |
| | A "PLAN REVIEW". |
| | PLEASE SEEE THIS IS NOW SUBMITTED UNDER |
| | THE 2004 FBC. |
| | |
| | 1) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| | MIN CALCULATIONS FOR RENOVATIONS TO |
| | EXISTING. |
| | PLEASE SEE PRESCRIPTIVE REQUIREMENTS |
| | AND FORM USE. PLEASE SEE THIS WILL ALSO |
| | BE IN THE MECHANICAL REVIEW NOTES. |
| | PLEASE SEE 13-413.1.ABC.1 FOR VOLTAGE |
| | DROP. |
| | PLEASE SEE A WORST CASE VOLTAGE DROP |
| | SHALL BE SHOWN ON PLANS. ONE FOR THE |
| | FEEDERS AND ONE FOR THE NEW BRANCH |
| | CIRCUITS. |
| | |
| | 2) NOTE: PLEASE SEE THE ONE LINE RISER |
| | DIAGRAM WHICH ONLY SHOWS ONE SET OF |
| | 500MCM'S TO EACH "AM" AND "BM". |
| | PLEASE SEE THIS SEEMS TO BE A MISPRINT |
| | AS ONE SETS TO EACH ONLY PROVIDES 400A'S |
| | WHEREAS THE MAINS ARE 800A. |
| | 310.16,240.4 ETC |
| | |
| | 3) NOTE: PLEASESHOW OR NOTE THAT THE |
| | CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| | ARE ALREADY FIGURED IN THE CALCULATIONS |
| | AT 125%. PLEASE REVISE CALCULATIONS TO |
| | INCLUDE THIS . |
| | 215.3, 230.42 |
| | |
| | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF ANY OF THE OLD REMOVED |
| | VOIDED SHEETS SHOULD BE SUBMITTED FOR |
| | REFERECNE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |