| 2006-06-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)PLANS ARE NOT SIGNED AND SEALED. |
| | |
| | 2.)INCLUDE GOVERNING CODE ON PLANS |
| | INDEX. |
| | |
| | 3.)DECLARE LEVEL OF ALTERATION FBC EB |
| | 3. |
| | |
| | 4.)CONSTRUCTION CLASS (PLANS INDEX) |
| | SHOULD INCLUDE TYPE A OR B.CONFIRM |
| | THAT YOU HAVE DECLARED THE CORRECT |
| | MINIMUM CONSTRUCTION TYPE, FBC 6. |
| | |
| | 5.)A-1 REFERS TO 713 JOINT SYSTEMS. |
| | PROVIDE A DETAIL. |
| | |
| | 6.)IF YOU ARE USING ALLOWABLE |
| | INCREASES AS INDICATED ON PLANS INDEX |
| | SHEET, PROVIDE CALCULATIONS.PROVIDE SF |
| | PER FLOOR. |
| | |
| | 7.)2ND FLOOR A2 SHOWS A JURY ROOM. |
| | COURTROOMS ARE A3 OCCUPANCY, 2 HOUR |
| | SEPARATION REQUIRED, FBC TABLE 302.3.2. |
| | |
| | |
| | |
| | |
| | |