2006-06-16 00:00:001. ALL CONSTRUCTION. DEMOLTION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. DEMOLTION WORK SHALL NOT INTERFERE
 WITH ANY REQUIRED EXITS SINCE IT IS THE
 INTENT TO HAVE PORTIONS REMAIN OCCUPIED.
  
 3. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 4. A REQUIRED FIRE WATCH IS REQUIRED
 WHEN ANY REQUIRED FIRE SYSTEM IS DOWN
 FOR MORE THAN FOUR HOURS. ALL FIRE
 WATCHES MUST BE APPROVED BY THE CHIEF
 FIRE PREVENTION OFFICER OR THE ASSISTANT
 FIRE MARSHAL.
  
 5. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE RELOCATION OF FIRE SPRINKLER
 HEADS.
  
 6. PLEASE INDICATE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 7. NEW FIRE DAMPERS AFTER INSTALLATION
 SHALL BE TESTED TO ENSURE PROPER
 OPERATION.
  
 8. PLEASE PROVIDE OCCUPANT LOADS FOR
 EACH ROOM IN THE SELECTIVE AREA OF
 DEMOLITION OR RENOVATION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER