2006-06-10 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE NOTES FROM BUILDING
 REVIEW WHICH MAY REQUIRE SOME DESIGN
 CHNAGES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 2) NOTE: PLEASE SEE THAT THE PLANS SHALL
 INDICATE THE WIND LOAD CALCULAITONS FOR
 THE NEW LT POLE BEING RELOCATED.
 PLEASE SEE THIS MUST MEET THE 140 MPH
 UNDER THE 2004 FBC. THE STRUCTURAL CALCS
 WILL BE REVIEWED BY THE BUILDING
 REVIEWER.
  
 3) NOTE: PLEASE SEE PLANS SEEM STO
 INDICATE THE CIRCUITING FOR EXSITING LTS
 TO A PANEL "A" WHICH IS NOT SHOWN,
 HOWEVER THE SOME RECEPTS ARE ALSO SHOWN
 CIRCUITED TO THE SAME "A" PANEL. THE
 QUESTION ARRISES AS THE FIXTURE SCHEDULE
 SHOWS THE NEW EXT LTS AS 277V?
 PLEASE CLARIFY AS THE LTS AND RECEPTS
 ARE CIRCUITED TO THE SAME PANEL.?
 ** PLEASE ALSO INCLUDE THE NEW FIXTURE
 TYPE/BRAND ETC FOR THE NEW EM LTS SHOWN
 ON PLANS.
  
 4) NOTE: PLEASE GIVE A BREAK DOWN AND
 LABEL EACH ROOM ARE DESIGNATION.
 PLEASE SEE PANEL SCHEDULE SHALL INDICATE
 THE ROOM IN WHICH THE CIRCUITS ARE
 SHOWN.
 408.4.
 PLEASE KNOW THE PANEL SCHEDULE ON SITE
 SHOULD BE LABELED FOR EACH ROOM AND OR
 AREA WHICH IS FED.
  
 5) NOTE: PLEASE SEE A BATTERY BACK UP
 FIXTURE OF SOME TYPE WILL BE REQUIRED
 FOR THE NEW EGREE RAMP. LS 101 7.8 ,7.9
 LIGHTING SHALL BE PROVIDED TO THE PUBLIC
 RIGHT OF WAY.
 THIS IS REQUIRED FOR NEW AND EXISTING
 DAY CARE OCCUPANCIES.
  
 PLEASE BE SURE TO COMPLETELY REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved