Plan Review Notes
Plan Review Notes For Permit 06050794
Permit Number 06050794
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-02 00:00:00PROVISO:
 PLEASE SEE COMMENTS FROM OTHER PLAN
 REVIEWERS.
2006-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050794
 ADD: 930 SOUTHERN BLVD.
 CONT: SEIRRAES CONST
 TEL: (561)848-6607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COVER SHEET CODE REVIEW CODE DATA:
 PLANS INDICATE TYPE OF CONSTRUCTION
 AS TYPEIV WHICH IS HEAVY CONSTRUCTION,
 UNPROTECTED ,SPRINKLERED PLEASE SEE
 TABLE 503 HEADINGS A OR B FOR THE AMOUNT
 OF FIRE RESISTANCE RATING.
  
 4) PROVIDE INFORMATION AS TO DESCRIPTION
 OF WORK, SEE 2004 EXISTING BUILDING CODE
 LEVEL 1, LEVEL 2 OR LEVEL 3. PROVIDE IN
 CODE REVIEW SUMMARY, SEE 2004 EXISTING
 BUILDING SECTION 303, 304 & 305.CHANGE
 OF OCCUPANCY.
  
 5) ADDITIONAL INFORMATION REQUIRED,
 CODE REVIEW COMMENT INDICATES DAY CARE
 SQ FT WAS 3260 AND INCREASED TO 6014 SQ
 FT. SHEET A.1 INDICATES NEW ROOMS TO BE
 MEETING ROOMS, ARE THESE ROOMS TO BE
 OCCUPIED BY THE DAY CARE OCCUPANCY?
  
 6)1033.6 SPECIAL MEANS OF EGRESS
 FEATURES.
 EVERY ROOM OR SPACE NORMALLY SUBJECT TO
 CLIENT OCCUPANCY, OTHER THAN BATHROOMS,
 SHALL HAVE AT LEAST ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE AND VENTILATION.
 SUCH WINDOW SHALL BE OPENABLE FROM THE
 INSIDE WITHOUT THE USE OF TOOLS AND
 SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN 20 INCHES (508 MM) WIDTH, 24
 INCHES (610 MM) IN HEIGHT, AND 5.7
 SQUARE FEET (0.53 M 2 ) IN AREA. THE
 BOTTOM OF THE OPENING SHALL BE NOT MORE
 THAN 44 INCHES (1118 MM) ABOVE THE
 FLOOR. THE CLEAR OPENING SHALL PERMIT A
 RECTANGULAR SOLID, WITH A MINIMUM WIDTH
 AND HEIGHT THAT PROVIDES THE REQUIRED
 5.7 SQUARE FOOT (0.53 M 2 ) OPENING AND
 A MINIMUM DEPTH OF 20 INCHES (8 MM), TO
 PASS FULLY THROUGH THE OPENING.
 EXCEPTIONS:
 1.IN BUILDINGS PROTECTED THROUGHOUT
 BY AN APPROVED, AUTOMATIC SPRINKLER
 SYSTEM.
 2.WHERE THE ROOM OR SPACE HAS A
 DOOR LEADING DIRECTLY TO THE OUTSIDE OF
 THE BUILDING.
  
 7)PROVIDE OCCUPANT LOAD IN EACH OF THE
 MEETING ROOMS. IT APPEARS THAT WHEN THE
 ACCORDIAN DOORS AND OR THE POCKET DOORS
 ARE CLOSED PLANS DO NOT MEET COMPLIANCE
 WITH:
 1033.2.1
 EVERY ROOM OR SPACE WITH AN OCCUPANT
 LOAD OF MORE THAN 50 PERSONS OR AN AREA
 OF MORE THAN 1,000 SQUARE FEET (93 M 2 )
 SHALL HAVE AT LEAST TWO EXIT ACCESS
 DOORWAYS AS REMOTELY LOCATED FROM EACH
 OTHER AS PRACTICABLE. SUCH DOORWAYS
 SHALL PROVIDE ACCESS TO SEPARATE EXITS,
 BUT WHERE EGRESS IS THROUGH CORRIDORS,
 THEY SHALL BE PERMITTED TO OPEN ONTO A
 COMMON CORRIDOR LEADING TO SEPARATE
 EXITS LOCATED IN OPPOSITE DIRECTIONS.
  
 8)SHEET A.1 DOESN'T INDICATE ANY WALL
 RATING ALONG THE EXIT ACCESS CORRIDOR AT
 THE DAY CARE AREA.SEE TABLE 1016.1 DAY
 CARE, OCUPANT LOAD > 30 AND WITH OUT
 FIRE SPRINKLER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  