| Plan Review Notes For Permit 06050785 |
| Permit Number |
06050785 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-26 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW FOR STORM DRAIN | | | ONLY TO FOUNDATION PERMIT #06020847 | | | | | | 1. SHEET U-P INDICATES A 10" STORM DRAIN | | | WITH FOUR BRANCHES AND THE END RUN | | | CAPPED, IS THIS THE INTENT, OR ARE THEY | | | TO TURN UP TO CATCH RISERS? MORE | | | INFORMATION REQUIRED | | | 2. PER SECTION 106.3.5.1.3 PLUMBING: A | | | STORM SYSTEM RISER DIAGRAM, WITH PIPE | | | SIZES, DRAIN LOCTIONS, AND SQUARE | | | FOOTAGE PER RISER AND TOTAL SQUARE | | | FOOTAGE FOR SYSTEM NEEDS TO BE INDICATED | | | ON DRAWING. | | | 3. PER TABLE 1102.4 PLEASE INICATE ON | | | SHEET U-P THE TYPE OF MATERIAL BEING | | | USED. | | | FOOTAGE OF AREAS TO BE DRAINED REQUIRED | | | 4. ANY PERMIT BEING DONE OFF OF A | | | FOUNDATION PERMIT WITH OUT A PLUMBING | | | PLAN REVIEW OF ENTIRE BUILDING TO BE | | | DONE AT OWN RISK. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|