| 2006-06-06 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 SEC. 424.2 OR |
| | FBC-2004 RESIDENTIAL SEC R4101 |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATION REQUIRED FOR PLAN REVIEW: |
| | |
| | 1) AS OF 10/1/05 FBC-2004 CODES WENT |
| | INTO EFFECT PLEASE CORRECTDRAWINGS TO |
| | REFLECT THE NEW CODE CHANGES FOR |
| | RESUBMITTAL. |
| | 2) COMPLY WITH FBC-2004 SEC 424.2, OR |
| | FBCR-2004 SEC R4101 PRIVATE SWIMMING |
| | POOLS.(PLEASE ADD TO NOTES FOR |
| | RESUBMITTAL) |
| | 3) FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| | SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| | ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 4) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004 |
| | SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL |
| | BE MOUNTED ON A SUBSTANTIAL BASE IN A |
| | MANNER THAT WILL ELIMINATE STRAIN ON |
| | PIPING.SLAB SHALL BE A NOMINAL 4" |
| | THICK. (DETAIL REQUIRED) |
| | 5) FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21,(ADD |
| | TO NOTES) |
| | 6) PLEASE ADD HEATER TO PIPING SCHEMATIC |
| | FOR RESUBMITTAL. |
| | 7) FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | 8) FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | 9) FBC-2004 SEC. 424.2.14.4, OR |
| | FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| | ALL WATER HEATING EQUIPMENT SHALL BE |
| | INSTALLED WITH FLANGES OR UNION |
| | CONNECTIONS ADJACENT TO THE HEATER. |
| | (ADD TO NOTES) |
| | 10) FBC-2004 SEC. 424.2.14, OR FBCR-2004 |
| | SEC. R4101.15 GAS PIPING SHALL COMPLY |
| | WITH FBC FUEL GAS.SEPARATE PLANS AND |
| | PERMIT REQUIRED.(ADD TO NOTES) |
| | 11) FBC-2004 SEC. 13-612.1.ABC.2.3.3 |
| | TIME CLOCKS SHALL BE INSTALLED ON |
| | PRIVATE POOLS.( PLEASE ADD TO DRAWING) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |