Plan Review Notes
Plan Review Notes For Permit 06050698
Permit Number 06050698
Review Stop G
Sequence Number 3
Notes
Date Text
2007-01-11 10:44:12DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS, FBC-2004 CHAPTER 1, AND
 FLORIDA ADMINISTRATIVE CODE
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PERMIT CAN NOT BE ISSUED WITH OUT A PERMIT
 APPLICATION. THERE WAS NOT A PERMIT APPLICATION WITH
 THIS RESUBMITTAL.
  
 2. NOTE: PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 A CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS REQUIRED IN THE TITLE BLOCK.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWING DOES NOT INDICATE ALL
 PIPING MATERIAL BEING INSTALLED OR ALL PIPE SIZES.
 PLEASE CORRECT AND RESUBMIT.
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: NOT ALL APPLIANCE BTU LOADS OR WHAT THE APPLIANCE
 IS ARE CLEARLY INDICATED ON THE RESUBMITTED DRAWING.
 PLEASE CORRECT AND RESUBMIT.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE RESUBMITTED DRAWINGS INDICATE A DELIVERY
 PRESSURE OF 0.5 TO 2.0 PSI. THIS IS WRONG. ON THE
 RESUBMITTAL ONLY ONE DELIVERY PRESSURE NEEDS TO BE
 INDICATED. DELIVERY PRESSURE IS EITHER GOING TO BE 0.5
 PSI OR IT IS GOING TO BE 2.0 PSI. PLEASE CORRECT AND
 RESUBMIT.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: MANUFACTURER CUT SHEETS OF GENERATOR AND IF GAS
 DELIVERY PRESSURE IS 2 PSI MANUFACTURER CUT SHEETS OF
 MP REGULATORS ARE NEEDED ON THE RESUBMITTAL.
  
 9. SHUT OFF VALVE AND REGULATOR IS MISSNG ON THE
 FIREPLACE.
  
 10. PER FBC-2004 CHAPTER 1, SECTION 106: ON THE
 RESUBMITTAL PLEASE SUBMIT DRAWINGS VOID OF HAND WRITTEN
 RED LINES UNLESS INITIALED AND DATED BY ENGINEER OF
 RECORD.
  
 *********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK HIGH LIGHTED YELLOW FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  