Plan Review Notes
Plan Review Notes For Permit 06050687
Permit Number 06050687
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM FIRST REVIEW, NOT
 ADDRESSED; NUMBERING REMAINING THE SAME
 FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2ND REVIEW - OVER 90 DAYS WITHOUT
 COMMENCING WORK, 713.13.PLEASE REFILE.
 THIS COMMENT MUST BE ADDRESSED PRIOR TO
 PERMIT PICKUP BUT DOES NOT PREVENT THE
 PERMIT FROM BEING ISSUED.
  
 2.)THE CALCS ARE TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002
 ON EACH SHEET.
  
 2ND REVIEW - NOT ADDRESSED.
  
 3.)GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.
  
 2ND REVIEW - NOT ADDRESSED.PLANS
 DECLARE FBC2001 HIGH VELOCITY.THIS IS
 NOT HIGH VELOCITY ZONE.HVHZ IS NOT
 ALWAYS MORE STRINGENT.PLANS ARE TO
 SHOW CODE COMPLIANCE WITH THE GOVERNING
 CODE.
  
 4.)CORRECT ASCE7 REFERENCE IS 02, NOT
 98, FBC35.
  
 NOT ADDRESSED.STILL STATES ASCE7-98.
  
 5-12.)ADDRESSED.
  
 13.)CLARIFY THE DIFFERENCE BETWEEN THE
 -74 PSF FOR ZONE 3, 500 SF, AND -78 FOR
 300 SF.YOU HAVE USED THE -74 DESIGN
 PRESSURE, BUT WHY IS THERE A MORE
 CONSERVATIVE NUMBER ON ANOTHER SHEET
 WHEN THE INFORMATION IS SPECIFIC TO THIS
 JOB?
  
 2ND REVIEW - NOT ADDRESSED.THERE ARE
 STILL DIFFERENT PRESSURE CONDITIONS ON
 THE COMPUTERIZED ENGINEERING.THE OLD
 ENGINEERING SHOWED A 25' HIGH, 146X44
 BUILDING.THE NEW ENGINEERING SHOWS A
 15' HIGH, 30X12 BUILDING.PROPERTY
 APPRAISER SHOWS SIX UNITS IN THIS
 BUILDING.CLARIFY DISCREPANCY IN
 BUILDING SIZE AS WELL AS THE DIFFERENCE
 IN PRESSURES.
  
 NEW COMMENTS:
  
 14.)CLARIFY WHY YOU HAVE USED 9.3
 INCHES FOR THE ROW SPACING IN THE
 CALCULATIONS.THE EXAMPLE IN THE BOOK,
 SAME CONDITIONS (36" SHEET, 4"LAP, 3
 ROWS) HAS A 10.67IN ROW SPACING.THE
 DIFFERENCE CHANGES THE FASTENING FOR
 ZONE 3 FROM 4.23 TO 3.5 FOR TWO ROWS, OR
 4.7 FOR 3 ROWS.
  
 15.)THE ENGINEERING HAS BEEN SENT TO
 FBPE.
  
 16.)SEE ATTACHED FS553.80(2)(B).
  
  
  
  