Plan Review Notes
Plan Review Notes For Permit 06050679
Permit Number 06050679
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.
  
 2.)THE CALCS ARE TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002
 ON EACH SHEET.
  
 3.)GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.
  
 4.)CORRECT ASCE7 REFERENCE IS 02, NOT
 98, FBC35.
  
 5.)FASTENING OF PLYWOOD AT 13", 8",
 AND 6" OC CONFLICTS WITH FBC TABLE
 2304.9.1.
  
 6.)RAS117 10.4.5, ALL FRACTIONS ARE TO
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
 YOU HAVE SPECIFIED 8.5 AND 4.6 FOR ZONE
 3 FASTENING.
  
 7.)THE FASTENING PATTERN SHOWN
 GRAPHICALLY ON THE RAS 117 CALCULATIONS
 ARE NOT CORRECT.YOU ARE SHOWING THE
 EQUIVALENT OF ONE ROW, 12"OC. THE SAME
 APPLIES TO FASTENING #2.IF YOU DO NOT
 UNDERSTAND THIS, SEE RAS117 AND THE
 EXAMPLE CALCULATION IN REGARDS TO
 DETERMINING HOW MANY FASTENERS PER
 SQUARE.
  
 8.)THE SPECIFICATION, FASTENING #1,
 FOR ZONE 3 IS NOT CLEAR.IT STATES 8.5"
 AT CORNERS STAGGERED IN TWO ROWS AT
 12"OC.ZONE 3 SHOULD BE TWO ROWS AT 8"
 OC.WHAT IS THE 12"OC?
  
 9.)YOU HAVE PROVIDED A SPECIFICATION,
 FASTENING #1, FOR ZONE 3, BUT NONE FOR
 ZONE 2.ACCORDING TO YOUR DESIGN
 PRESSURES, ENHANCED FASTENING REQUIRED
 FOR ZONE 2.
  
 10.) THE SPECIFICATION, FASTENING #2,
 DOES NOT HAVE A SPECIFICATION FOR ZONE
 2.
  
 11.)THE SIGNATURES APPEAR TO BE A
 PHOTOCOPY.ORIGINAL WET SIGNATURE
 REQUIRED PER FBPE.
  
 12.)INITIALS ARE NOT ACCEPTABLE AS A
 SIGNATURE PER FBPE.
  
 13.)THE CALCULATIONS FOR THE ROOF
 SHEATHING ARE NOT CLEAR.ISN'T THE ROOF
 SHEATHING A PART OF THE MWFRS, NOT
 COMPONENTS AND CLADDING?THIS COMMENT
 DOES NOT NEED TO BE ADDRESSED AS YOU
 CANNOT SPECIFY FASTENING WHICH IS LESS
 THAN MINIMUM CODE REQUIREMENTS.