| 2006-05-16 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713. |
| | |
| | 2.)THE CALCS ARE TO HAVE ALL |
| | INFORMATION REQUIRED BY FAC61G15-23.002 |
| | ON EACH SHEET. |
| | |
| | 3.)GOVERNING CODE IS FBC2004 EFFECTIVE |
| | OCTOBER 1, 2005. |
| | |
| | 4.)CORRECT ASCE7 REFERENCE IS 02, NOT |
| | 98, FBC35. |
| | |
| | 5.)FASTENING OF PLYWOOD AT 13", 8", |
| | AND 6" OC CONFLICTS WITH FBC TABLE |
| | 2304.9.1. |
| | |
| | 6.)RAS117 10.4.5, ALL FRACTIONS ARE TO |
| | ROUNDED DOWN TO THE NEXT WHOLE NUMBER. |
| | YOU HAVE SPECIFIED 8.5 AND 4.6 FOR ZONE |
| | 3 FASTENING. |
| | |
| | 7.)THE FASTENING PATTERN SHOWN |
| | GRAPHICALLY ON THE RAS 117 CALCULATIONS |
| | ARE NOT CORRECT.YOU ARE SHOWING THE |
| | EQUIVALENT OF ONE ROW, 12"OC. THE SAME |
| | APPLIES TO FASTENING #2.IF YOU DO NOT |
| | UNDERSTAND THIS, SEE RAS117 AND THE |
| | EXAMPLE CALCULATION IN REGARDS TO |
| | DETERMINING HOW MANY FASTENERS PER |
| | SQUARE. |
| | |
| | 8.)THE SPECIFICATION, FASTENING #1, |
| | FOR ZONE 3 IS NOT CLEAR.IT STATES 8.5" |
| | AT CORNERS STAGGERED IN TWO ROWS AT |
| | 12"OC.ZONE 3 SHOULD BE TWO ROWS AT 8" |
| | OC.WHAT IS THE 12"OC? |
| | |
| | 9.)YOU HAVE PROVIDED A SPECIFICATION, |
| | FASTENING #1, FOR ZONE 3, BUT NONE FOR |
| | ZONE 2.ACCORDING TO YOUR DESIGN |
| | PRESSURES, ENHANCED FASTENING REQUIRED |
| | FOR ZONE 2. |
| | |
| | 10.) THE SPECIFICATION, FASTENING #2, |
| | DOES NOT HAVE A SPECIFICATION FOR ZONE |
| | 2. |
| | |
| | 11.)THE SIGNATURES APPEAR TO BE A |
| | PHOTOCOPY.ORIGINAL WET SIGNATURE |
| | REQUIRED PER FBPE. |
| | |
| | 12.)INITIALS ARE NOT ACCEPTABLE AS A |
| | SIGNATURE PER FBPE. |
| | |
| | 13.)THE CALCULATIONS FOR THE ROOF |
| | SHEATHING ARE NOT CLEAR.ISN'T THE ROOF |
| | SHEATHING A PART OF THE MWFRS, NOT |
| | COMPONENTS AND CLADDING?THIS COMMENT |
| | DOES NOT NEED TO BE ADDRESSED AS YOU |
| | CANNOT SPECIFY FASTENING WHICH IS LESS |
| | THAN MINIMUM CODE REQUIREMENTS. |