2006-05-23 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. PER FBC-2004 CHAPTER 1, THE FOLLWING
 IS REQUIRED ON THE ISOMETRIC PLUMBING
 RISER DIAGRAM.
 (A) 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS. NOTE: THE DOUBLE
 BOWL KITCHEN SINK WITH DISHWASHER IN
 ROOM #105 NEEDS TO BE INDICATED AND ONLY
 ONE LAV IS INDICATED FOR ROOM #203 THERE
 ARE TWO THAT NEED TO BE INDICATED.
 PLEASE SEE CORRECTED DRAWING ON SHEET
 P-1 FOR RESUBMITTAL REFERENCE FOR THE
 ABOVE OTHER REQUIREMENTS.
 2. PER FBC-2004 PLUMBING, THE FOLLOWING
 IS REQUIRED ON THE ISOMETRIC PLUMBING
 RISER DIAGRAM PRETAINING TO THE WASHING
 MACHINES IN ROOM #106
 (A) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPES
 ON DRAWING FOR RESUBMITTAL.
 (B) THE WASHING MACHINE IS NOT VENTED
 PER, 908.3 CONNECTIONS AT DIFFERENT
 LEVELS. WHERE THE FIXTURE DRAINS CONNECT
 AT DIFFERENT LEVELS, THE VENT SHALL
 CONNECT AS A VERTICAL EXTENTION OF THE
 VERTICAL DRAIN. THE UPPER FIXTURE SHALL
 NOT BE A WATER CLOSET. PLEASE SEE
 CORRECTED DRAWING ON SHEET P-1 FOR
 RESUBMITTAL REFERENCE.
 3. PER FBC-2004 PLUMBING, THE FOLLOWING
 CORRECTIONS ARE REQUIRED FOR ROOM #107.
 (A) THE SHOWER IS NOT VENTED PER 902.2.1
 (B) THE HORIZONTAL DRY VENT INDICATED
 FOR THE WATER CLOSET IS NOT ALLOWED PER
 905.3
 4. PER FBC-2004 PLUMBING, THE FOLLOWING
 CORRECTIONS ARE REQUIRED FOR ROOM #205.
 (A) SHOWER INDICATES A "S" TRAP, "S"
 TRAPS PROHIBITED PER 1002.3
 (B) THE HORIZONTAL DRY VENT INDICATED ON
 THE TUB NOT ALLOWED PER 905.3
 5. PER FBC-2004 PLUMBING, SECTION 916.2
 VENTS OTHER THAN STACK VENTS OR VENT
 STACKS. VENTS EXCEEDING 40 FEET(12192MM)
 IN DEVELOPED LENGTH SHALL BE INCREASED
 BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE. NOTE:
 PLEASE REFERENCE CORRECTED PLBG. ISO.
 RISER DIAGRAM ON SHEET P-1 FOR
 RESUBMITTAL.
 6. PLEASE NOTE THE CLEANOUT LOCATIONS ON
 THE CORRECTED PLBG. ISO. RISER DIAGRAM
 FOR REFERENCE FOR RESUBMITTAL.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 7. ON SHEET A-2 IN THE BOXES 03 AND 04
 THE SCALE INDICATED 1"=1'-0" IS WRONG,
 IT SHOULD BE 1/4"=1'-0" PLEASE CORRECT
 FOR RESUBMITTAL.
  
 END OF COMMENTS:
  