Plan Review Notes
Plan Review Notes For Permit 06050665
Permit Number 06050665
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-24 00:00:00*** DENIED ***
 1) PLEASE SHOW LISTING OF EXISTING A/C
 EQUIPMENT ON MECHHANICAL PLAN.
  
 2) SHOW SIZE OF MAIN SUPPLY AIR DUCT
 RUNNING ALONG FAMILY ROOM WALL.
  
 3) SHOW IF AHU #1 IS IN A CLOSET OR
 ATTIC.
  
 4) SHOW CLOTHES DRYER VENT TERMINATION,
 PER 2004 FBC/M 501.2 .
  
 5) SUBMIT MANUAL "D" CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601 .
  
 6) PLEASE PROVIDE RETURN AIR FOR
 BEDROOMS, PER 2004 FBC/R M1602.4, OR
 PROVIDE FBC THAT EXEMPTS THIS HOME.
  
 7) PLEASE EXPLAIN WHAT "VS" MEANS AT
 SUPPLY AIR GRILLS IN FAMILY ROOM AND
 LIVING ROOM.
  
 8) PLEASE NOTE THAT THE ARCHITECT'S SEAL
 IS MISSING FROM MECHANICAL PLANS, PLEASE
 COMPLY WITH FS 61G1-16.003 .
  
 9)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 10) PLEASE HAVE ENERGY CAL'S. SIGNED BY
 OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.