| Plan Review Notes For Permit 06050665 |
| Permit Number |
06050665 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-24 00:00:00 | *** DENIED *** | | | 1) PLEASE SHOW LISTING OF EXISTING A/C | | | EQUIPMENT ON MECHHANICAL PLAN. | | | | | | 2) SHOW SIZE OF MAIN SUPPLY AIR DUCT | | | RUNNING ALONG FAMILY ROOM WALL. | | | | | | 3) SHOW IF AHU #1 IS IN A CLOSET OR | | | ATTIC. | | | | | | 4) SHOW CLOTHES DRYER VENT TERMINATION, | | | PER 2004 FBC/M 501.2 . | | | | | | 5) SUBMIT MANUAL "D" CALCULATIONS FOR | | | RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R | | | M1601 . | | | | | | 6) PLEASE PROVIDE RETURN AIR FOR | | | BEDROOMS, PER 2004 FBC/R M1602.4, OR | | | PROVIDE FBC THAT EXEMPTS THIS HOME. | | | | | | 7) PLEASE EXPLAIN WHAT "VS" MEANS AT | | | SUPPLY AIR GRILLS IN FAMILY ROOM AND | | | LIVING ROOM. | | | | | | 8) PLEASE NOTE THAT THE ARCHITECT'S SEAL | | | IS MISSING FROM MECHANICAL PLANS, PLEASE | | | COMPLY WITH FS 61G1-16.003 . | | | | | | 9)ENERGY CALCULATIONS NEED TO BE ON FORM | | | 600A-04 (2004) PER FBC 13-600.3.A . | | | | | | 10) PLEASE HAVE ENERGY CAL'S. SIGNED BY | | | OWNER/AGENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|