| 2006-05-22 00:00:00 | NONCOMPLIANT |
| | ~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE ENGINEER OF RECORD SHALL INDICATE |
| | THE CERTIFICATE OF AUTHORIZATIONNUMBER |
| | ALONG WITH OTHER INFORMATION REQUIRED BY |
| | 61G15-23.002FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 2} 210.52(C)(1) WALL COUNTER SPACES. A |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| | EACH WALL COUNTER SPACE THAT IS 300 MM |
| | (12 IN.) OR WIDER. RECEPTACLE OUTLETS |
| | SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 600 MM |
| | (24 IN.) MEASURED HORIZONTALLY FROM A |
| | RECEPTACLE OUTLET IN THAT SPACE. SEE |
| | KITCHEN , ELECTRICAL PLAN, REVIEWED SET. |
| | |
| | 3) 210.52 DWELLING UNIT RECEPTACLE |
| | OUTLETS. |
| | (A)(1) SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SO THAT NO POINT MEASURED |
| | HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| | WALL SPACE IS MORE THAN 1.8 M (6 FT) |
| | FROM A RECEPTACLE OUTLET. |
| | (A)(2)(1)ANY SPACE 600 MM (2 FT) OR MORE |
| | IN WIDTH (INCLUDING SPACE MEASURED |
| | AROUND CORNERS) AND UNBROKEN ALONG THE |
| | FLOOR LINE BY DOORWAYS, FIREPLACES, AND |
| | SIMILAR OPENINGS. SEE LIVING ROOM, AND |
| | BOTH BEDROOMS UPSTAIRS. |
| | |
| | 4} A SMOKE DETECTOR IS REQUIRED IN THE |
| | HALL AT THE STAIRS ON THE SECOND FLOOR, |
| | PER R313.1, 2&3. |
| | |
| | 5} PLEASE INDICATE THE INTENT OF THE TWO |
| | RECEPTACLES LOCATED OFF THE WALL IN THE |
| | MASTER BEDROOM. ARE THESE IN THE CEILING |
| | POSSIBLY, OR LOCATEED AS FLOOR BOXES OFF |
| | THE WALL? |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |
| | |