Plan Review Notes
Plan Review Notes For Permit 06050665
Permit Number 06050665
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-22 00:00:00NONCOMPLIANT
 ~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY
 61G15-23.002FLORIDA ADMINISTRATIVE
 CODE.
  
 2} 210.52(C)(1) WALL COUNTER SPACES. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH WALL COUNTER SPACE THAT IS 300 MM
 (12 IN.) OR WIDER. RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM
 (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. SEE
 KITCHEN , ELECTRICAL PLAN, REVIEWED SET.
  
 3) 210.52 DWELLING UNIT RECEPTACLE
 OUTLETS.
 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED
 HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT)
 FROM A RECEPTACLE OUTLET.
 (A)(2)(1)ANY SPACE 600 MM (2 FT) OR MORE
 IN WIDTH (INCLUDING SPACE MEASURED
 AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS, FIREPLACES, AND
 SIMILAR OPENINGS. SEE LIVING ROOM, AND
 BOTH BEDROOMS UPSTAIRS.
  
 4} A SMOKE DETECTOR IS REQUIRED IN THE
 HALL AT THE STAIRS ON THE SECOND FLOOR,
 PER R313.1, 2&3.
  
 5} PLEASE INDICATE THE INTENT OF THE TWO
 RECEPTACLES LOCATED OFF THE WALL IN THE
 MASTER BEDROOM. ARE THESE IN THE CEILING
 POSSIBLY, OR LOCATEED AS FLOOR BOXES OFF
 THE WALL?
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  