| 2006-05-24 00:00:00 | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ***PARTIAL PLAN REVIEW, PENDING PRODUCT |
| | APPROVAL COMMENTS*** |
| | |
| | SEE PERMIT 06010836.A PERMIT HAS |
| | ALREADY BEEN APPLIED FOR.PLEASE VOID |
| | ONE OF THE PERMITS (SUBMIT A LETTER). |
| | |
| | 1.)INCLUDE THE ENGINEER'S INFORMATION |
| | ON THE PRODUCT APPROVAL APPLICATION. |
| | |
| | 2.)DESIGNER OF RECORD IS TO REVIEW THE |
| | PRODUCT APPROVAL, FBC*106.3.3.A LETTER |
| | WAS PROVIDED, BUT IS REQUIRED TO BE A |
| | SIGNED, SEALED, DATED ORIGINAL |
| | FAC61G1-16, AND IS TO HAVE A CONCLUSION |
| | IN REGARDS TO THIS PRODUCT IN THIS |
| | APPLICATION.THE LETTER REFERS TO THE |
| | FIRST PERMIT NUMBER RATHER THAN THIS NEW |
| | PERMIT NUMBER. |
| | |
| | 3.)PROVIDE WIND DESIGN CRITERIA |
| | FBC1603.1.4.THIS IS TO INCLUDE ALL |
| | ITEMS, INCLUDING DESIGN PRESSURES FOR |
| | THE METAL ROOF. |
| | |
| | 4.)DECLARE GOVERNING CODE. |
| | |
| | 5.)THE DETAILS SUBMITTED SHOW |
| | CONSTRUCTION OF AN |
| | ENTRY, INCLUDING STRUCTURAL ELEMENTS AND |
| | ELECTRIC.THIS IS NOT |
| | WITHIN THE SCOPE OF A ROOFING |
| | CONTRACTOR'S LICENSE.IT APPEARS THAT |
| | SOME OF THE PLANS SUBMITTED SHOW |
| | EXISTING CONDITIONS.ANY PLANS |
| | SUBMITTED SHOULD SHOW CODE COMPLIANCE |
| | FOR THE PROPOSED WORK.THE PLANS, |
| | CONSTRUCTION OF AN ENTRY, ARE NOT |
| | CONSISTENT WITH THE APPLICATION, |
| | INSTALLING A METAL ROOF. |
| | |
| | SHEET A900 PROVIDES DETAILS FOR THE |
| | REPAIR.PROVIDE METAL FRAMING SPACING, |
| | SEE THE LOAD SCHEDULE ON THE PRODUCT |
| | APPROVAL.CODE COMPLIANCE CANNOT BE |
| | DETERMINED WITHOUT THIS INFORMATION. |
| | |
| | 6.)THE PLANS SUBMITTED SHOW A PLYWOOD |
| | DECK.IF THIS IS EXISTING, NOT |
| | PROPOSED, PROVIDE A PERMIT NUMBER. |
| | COMBUSTIBLES WERE NOT ALLOWED IN TYPE I |
| | AND II CONSTRUCTION UNDER THE CODE IN |
| | EFFECT ON THE DATE ON THE PLAN, 1999. |
| | PROVIDE BUILDING TYPE FBC6 AND AREA |
| | FBC5.INDICATE IF THIS BUILDING IS |
| | SPRINKLED.IF THIS AREA WAS NOT BUILT |
| | IN COMPLIANCE WITH THE CODE IN EFFECT AT |
| | THE TIME OF CONSTRUCTION, THIS MUST BE |
| | ADDRESSED. |
| | |