| 2006-07-10 00:00:00 | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 6-1-06 | | | NOTE #7, PLEASE SHOW CFM'S AT EACH | | | SUPPLY AIR GRILL. | | | | | | 2) SEE SUBMITTED MANUAL J CALCULATIONS | | | "CFM'S PER ROOM", MOST SUPPLY AIR DUCTS | | | TO ROOMS ARE OVER SIZED, PLEASE CORRECT. | | | | | | 3) ONLY ONE ENERGY CALCULATION WAS | | | SIGNED, PLEASE SIGN OTHER COPY. | | | | | | 4) PLEASE SHOW SIZE OF RETURN AIR DUCT | | | TO 24X14 RETURN AIR GRILL IN HALLWAY. | | | | | | 5) PLEASE SEE ATTACHED MANUAL 'D' COVER | | | AND RECOMMENED VELOCITY. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|