2006-07-10 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 6-1-06
 NOTE #7, PLEASE SHOW CFM'S AT EACH
 SUPPLY AIR GRILL.
  
 2) SEE SUBMITTED MANUAL J CALCULATIONS
 "CFM'S PER ROOM", MOST SUPPLY AIR DUCTS
 TO ROOMS ARE OVER SIZED, PLEASE CORRECT.
  
 3) ONLY ONE ENERGY CALCULATION WAS
 SIGNED, PLEASE SIGN OTHER COPY.
  
 4) PLEASE SHOW SIZE OF RETURN AIR DUCT
 TO 24X14 RETURN AIR GRILL IN HALLWAY.
  
 5) PLEASE SEE ATTACHED MANUAL 'D' COVER
 AND RECOMMENED VELOCITY.
  