| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE RANGE OCP IS INCORRECT. CIRCUIT | | | 9,11. 310.16 | | | | | | 2) THE AHU IS INCORRECT PER 310.16 | | | | | | 3) THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 4) THE SERVICE AND FEEDER CONDUCTORS ARE | | | INCORRECT PER 310.15(B)(6). MINIMUM OF | | | 2/0 CU FOR A 200 AMP SERVICE. | | | | | | 5) THE RISER DIAGRAM INDICATES A METER | | | WITH A SEPARATE DISCONNECT. THE PLAN | | | SHOWS A METER/MAIN COMBINATION. PLEASE | | | CORRELATE. | | | | | | PLEASE CORRECT THE COVER SHEET REGARDING | | | THE INDEX SHEET. THE ELECTRICAL PLAN IS | | | ON 7.1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|