2006-06-02 00:00:00DENIED;
 1. AUTOMATIC CLOTHES WASHWER DISCHARGE
 PIPE REQUIRED TO BE 3" FBC-2004 PLUMBING
 SEC.406.3 AND MUST DISCHARGE DOWN STREAM
 OF A BATHROOM GROUP SEC. 909.1.
 2.RISER DIAGRAM VENT SYSTEM NOT CORRECT,
 1/2 THE VENTS ARE NOT REQUIRED. ( SEE
 ONE SET OF PLANS MARKED IN RED)