Plan Review Notes
Plan Review Notes For Permit 06050642
Permit Number 06050642
Review Stop M
Sequence Number 1
Notes
Date Text
2006-06-01 00:00:00*** DENIED ***
 1) NEED A/C EQUIPMENT LISTING ON
 MECHANICAL PLANS.
  
 2) PLANS SHOW NO RETURN AIR DUCTS OR
 GRILL SIZES TO BEDROOMS, PLEASE CORRECT.
  
 3) PLEASE SHOW DUCT LAY-OUT AS A RIDGED
 RECTANGULAR TRUNK LINE WITH FLEX DROPS,
 OR AS A ALL FLEX WITH MIXING BOXES
 (SPIDER LAY-OUT) AND SHOW CORRECT DUCT
 SIZES.
  
 4) SHOW CLOTHES DRYER VENT LOCATION ON
 MECH. PLANS.
  
 5) SHOW CONDENSATE DRAIN LINE LOCATION
 ON MECH. PLANS.
  
 6) HAVE ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT.
  
 7) SHOW CFM'S AT EACH SUPPLY AIR GRILL.
  
 8) SUBMIT MANUAL 'D' CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER2004 BBC/R
 M1601.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  