| Plan Review Notes For Permit 06050642 |
| Permit Number |
06050642 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-01 00:00:00 | *** DENIED *** | | | 1) NEED A/C EQUIPMENT LISTING ON | | | MECHANICAL PLANS. | | | | | | 2) PLANS SHOW NO RETURN AIR DUCTS OR | | | GRILL SIZES TO BEDROOMS, PLEASE CORRECT. | | | | | | 3) PLEASE SHOW DUCT LAY-OUT AS A RIDGED | | | RECTANGULAR TRUNK LINE WITH FLEX DROPS, | | | OR AS A ALL FLEX WITH MIXING BOXES | | | (SPIDER LAY-OUT) AND SHOW CORRECT DUCT | | | SIZES. | | | | | | 4) SHOW CLOTHES DRYER VENT LOCATION ON | | | MECH. PLANS. | | | | | | 5) SHOW CONDENSATE DRAIN LINE LOCATION | | | ON MECH. PLANS. | | | | | | 6) HAVE ENERGY CALCULATIONS SIGNED BY | | | OWNER/AGENT. | | | | | | 7) SHOW CFM'S AT EACH SUPPLY AIR GRILL. | | | | | | 8) SUBMIT MANUAL 'D' CALCULATIONS FOR | | | RESIDENTIAL DUCT DESIGN, PER2004 BBC/R | | | M1601.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|