| 2006-06-01 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} LOCATE THE SERVICE DISCONNECT ON THE |
| | PLAN. |
| | |
| | 3} INDICATE COMPLIANCE WITH ARTICLE |
| | 250.50 FOR THE GROUNDING ELECTRODE |
| | SYSTEM. ALL AVAILABLE MUST BE USED ON |
| | THE RISER. SIZE GEC PER 250.66. |
| | |
| | 4} NOTE #1 INCORRECTLY REFERENCES THE |
| | 2005 NEC. WE ARE CURRENTLY USING THE |
| | 2002 NEC AS ADOPTED 553.73 FS. |
| | |
| | 5} THE 80 AMP OCP WITH #6 CONDUCTOR, |
| | CIRCUITS #1,3-2,4 IS IN VIOLATION OF |
| | 310.16. |
| | |
| | 6} THE BATH FANS AND RECEPTACLES ON ONE |
| | CIRCUIT , TWO BATHS, ARE IN VIOLATION OF |
| | 210.11(C)(3). SHOW ON SCHEDULE. |
| | |
| | 7} THE RANGE OCP IS INCORRECT. CIRCUIT |
| | 9,11. |
| | |
| | 8} THE MICROWAVE SHOWN ON THE PLAN IS |
| | NOT ON THE SCHEDULE AND THEREFORE NOT IN |
| | THE CALCULATION. ADD SAME. |
| | |
| | 8} 210.52(E) OUTDOOR OUTLETS. FOR A |
| | ONE-FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE AT GRADE LEVEL AND NOT MORE |
| | THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL |
| | BE INSTALLED AT THE FRONT AND BACK OF |
| | THE DWELLING. SEE 210.8(A)(3). |
| | |
| | 9} THE PERSON TAKING RESPONSIBILITY FOR |
| | THE DESIGN MUST PRINT AND SIGN THEIR |
| | NAME TO SAME PER 106.3.4.2. |
| | |
| | PLEASE CORRECT THE COVER SHEET REGARDING |
| | THE INDEX SHEET. THE ELECTRICAL PLAN IS |
| | ON 7.1. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |