Plan Review Notes
Plan Review Notes For Permit 06050642
Permit Number 06050642
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-01 00:00:00 
 NONCOMPLIANT
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} LOCATE THE SERVICE DISCONNECT ON THE
 PLAN.
  
 3} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SIZE GEC PER 250.66.
  
 4} NOTE #1 INCORRECTLY REFERENCES THE
 2005 NEC. WE ARE CURRENTLY USING THE
 2002 NEC AS ADOPTED 553.73 FS.
  
 5} THE 80 AMP OCP WITH #6 CONDUCTOR,
 CIRCUITS #1,3-2,4 IS IN VIOLATION OF
 310.16.
  
 6} THE BATH FANS AND RECEPTACLES ON ONE
 CIRCUIT , TWO BATHS, ARE IN VIOLATION OF
 210.11(C)(3). SHOW ON SCHEDULE.
  
 7} THE RANGE OCP IS INCORRECT. CIRCUIT
 9,11.
  
 8} THE MICROWAVE SHOWN ON THE PLAN IS
 NOT ON THE SCHEDULE AND THEREFORE NOT IN
 THE CALCULATION. ADD SAME.
  
 8} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 9} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 PLEASE CORRECT THE COVER SHEET REGARDING
 THE INDEX SHEET. THE ELECTRICAL PLAN IS
 ON 7.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  