| Plan Review Notes For Permit 06050627 |
| Permit Number |
06050627 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-21 00:00:00 | ***DENIED*** | | | | | | 1) CALCULATION SHEETS INDICATE A SAFETY | | | MARGIN OF 4.928 PSI. PLEASE NOTE THAT A | | | MINIMUM SAFETY MARGIN OF 5 IS REQUIRED | | | IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|