Review Stop E
Sequence Number 3
Notes
Date Text
2006-08-03 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 1" FEEDER TO PANEL "L2" IS TOO
 SMALL FOR THE FEED CONDUCTORS.
  
 2} PLEASE INDICATE THE LOCATION OF THE
 OVERCURRENT PROTECTION FOR PANEL "L2",
 AND SECONDARY PROTECTION FOR THE 30K
 TRANSFORMER.
  
 3} THE CIRCUIT NUMBERS FOR THE LIGHTS
 AND ON THE PLAN AND THE PANEL SCHEDULE
 DO NOT CORRELATE.
  
 4} INDICATE THE LOCATIONS OF THE EXIT
 AND EMERGENCY LIGHTING, AND LABEL SAME
 WITH CIRCUIT NUMBERS.
  