| Date |
Text |
| 2006-08-03 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 1" FEEDER TO PANEL "L2" IS TOO | | | SMALL FOR THE FEED CONDUCTORS. | | | | | | 2} PLEASE INDICATE THE LOCATION OF THE | | | OVERCURRENT PROTECTION FOR PANEL "L2", | | | AND SECONDARY PROTECTION FOR THE 30K | | | TRANSFORMER. | | | | | | 3} THE CIRCUIT NUMBERS FOR THE LIGHTS | | | AND ON THE PLAN AND THE PANEL SCHEDULE | | | DO NOT CORRELATE. | | | | | | 4} INDICATE THE LOCATIONS OF THE EXIT | | | AND EMERGENCY LIGHTING, AND LABEL SAME | | | WITH CIRCUIT NUMBERS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|