| Plan Review Notes For Permit 06050625 |
| Permit Number |
06050625 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-07-07 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE SCOPE OF THIS WORK REQUIRES | | | ENGINEERING PER 471 FS. | | | PLEASE HAVE AN ENGINEER DESIGN THE PLAN | | | AND RESUBMIT. THE TERM "ENGINEER" | | | APPLIES TO A PERSON LICENSED UNDER | | | CHAPTER 471 FS. THE ARCHITECTDID NOT | | | SEAL PAGE E-2, WHICH IS INCEDENTAL TO | | | HIS DESIGN. HE, OR THE ENGINEER TAKING | | | RESPONSIBILITY FOR THE SERVICE DRAWING, | | | MUST SIGN AN DSEAL THIS SHEEET PR EITHER | | | 471 OR 481.FS | | | | | | 2} INCLUDE ALL EQUIPMENT (PANELS "L" AND | | | "H"), ON THE RISER. | | | | | | 3} PANEL SCHEDULE "H" DOES NOT SHOW A | | | FEED FOR THE 30 KVA TRANSFORMER. SHOW | | | PANEL "H" ON THE RISER. | | | | | | 4} PANEL "L2" IS LISTED AS "MLO", | | | THEREFORE THE TRANSFORMER FEEDING IT HAS | | | NO SECONDARY PROTECTION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|