2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SCOPE OF THIS WORK REQUIRES
 ENGINEERING PER 471 FS.
 PLEASE HAVE AN ENGINEER DESIGN THE PLAN
 AND RESUBMIT. THE TERM "ENGINEER"
 APPLIES TO A PERSON LICENSED UNDER
 CHAPTER 471 FS. THE ARCHITECTDID NOT
 SEAL PAGE E-2, WHICH IS INCEDENTAL TO
 HIS DESIGN. HE, OR THE ENGINEER TAKING
 RESPONSIBILITY FOR THE SERVICE DRAWING,
 MUST SIGN AN DSEAL THIS SHEEET PR EITHER
 471 OR 481.FS
  
 2} INCLUDE ALL EQUIPMENT (PANELS "L" AND
 "H"), ON THE RISER.
  
 3} PANEL SCHEDULE "H" DOES NOT SHOW A
 FEED FOR THE 30 KVA TRANSFORMER. SHOW
 PANEL "H" ON THE RISER.
  
 4} PANEL "L2" IS LISTED AS "MLO",
 THEREFORE THE TRANSFORMER FEEDING IT HAS
 NO SECONDARY PROTECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  