2007-03-13 15:45:19** MECHANICAL REVISION **
 *** DENIED ***
 1) PLEASE PROVIDE RETURN AIR TO PLAYROOM, PER 2004
 FBC/R M1602.4.
  
 2) PLEASE SHOW THE SIZE OF THE TWO SUPPLY AIR DUCTS
 FROM AHU #2 TO THE TWO MIXING BOXES (SEE YELLOW
 HIGHLIGHT ON PLANS PAGE M-1).
  
 3) REVISED MECHANICAL PLANS ARE SHOWING A 6" PIPE TO
 THE EXISTING STOVE IN THE EXISTING KITCHEN, IF PIPE IS
 NEW SHOW WHAT IT IS FOR, TYPE OF MATERIAL, AND WERE
 PIPE TERMINATES.
  