| Plan Review Notes For Permit 06050609 |
| Permit Number |
06050609 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-13 15:45:19 | ** MECHANICAL REVISION ** | | | *** DENIED *** | | | 1) PLEASE PROVIDE RETURN AIR TO PLAYROOM, PER 2004 | | | FBC/R M1602.4. | | | | | | 2) PLEASE SHOW THE SIZE OF THE TWO SUPPLY AIR DUCTS | | | FROM AHU #2 TO THE TWO MIXING BOXES (SEE YELLOW | | | HIGHLIGHT ON PLANS PAGE M-1). | | | | | | 3) REVISED MECHANICAL PLANS ARE SHOWING A 6" PIPE TO | | | THE EXISTING STOVE IN THE EXISTING KITCHEN, IF PIPE IS | | | NEW SHOW WHAT IT IS FOR, TYPE OF MATERIAL, AND WERE | | | PIPE TERMINATES. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|