| Plan Review Notes For Permit 06050609 |
| Permit Number |
06050609 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-13 10:52:12 | | | | | | | REVISION DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE LOAD CALCULATION, AFTER DEMAND FACTORS ARE TAKEN | | | , IS LARGER THAN THE PROPOSED SERVICE. SEE 220 PART II. | | | INDICATE IF USING THE STANDARD CALCULATION IN 220 PART | | | I, OR THE OPTIONAL CALCULATION (PREFERRED), 220.31(B). | | | PLEASE SEE 230.31(B) MUST BE USED BECAUSE OF THE | | | ADDITIONAL A/C LOADS. | | | | | | 2} THE BATH CIRCUITS SHOWN AS HOME RUNS ON SHEET E-1, | | | THIS REVISION, ARE NOT LISTED ON THE PANEL SCHEDULE. AS | | | REQUIRED PER210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|