| Plan Review Notes For Permit 06050609 |
| Permit Number |
06050609 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-14 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT, PER 2004 | | | FBC/13-600.3.ABC.2 . | | | | | | 2) "TITLE BLOCK" ARCHITECT PRINTED NAME, | | | AND THE FIRM'S LICENSE NUMBER MUST | | | APPEAR IN THE TITLE BLOCK, PER FAC | | | 61G1-16.003 . | | | | | | 3) SHOW SUPPLY AIR CFM'S. AT ALL SUPPLY | | | AIR GRILLS. | | | | | | 4) AHU #3 PLEASE SHOW CORRECT SIZES FOR | | | MAIN SUPPLY AIR TRUNK LINE. | | | | | | 5) SHOW LOCATION AND TERMINATION OF | | | CLOTHES DRYER VENT. | | | | | | 6) PLEASE PROVIDE COMBUSTION AIR, OR | | | COMBUSTION AIR CALCULATIONS FOR GAS | | | WATER, PER 2004 FBC/M 701. | | | | | | 7) PLEASE PROVIDE A APPROVED EXHAUST | | | HOOD FOR THE GRILL IN THE COVERED LOGGIA | | | WITH DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS, OR PROVIDE GRILL | | | MANUFACTURE'S SPECIFICATION'S SHOWING | | | ONE IS NOT REQUIRED, PER 2004 FBC/M | | | 505.3 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|