| Plan Review Notes For Permit 06050604 |
| Permit Number |
06050604 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-23 13:17:28 | FAILED FOR FOLLOWING REASONS: | | | | | | 1 PLEASE CALCULATE THE WORST CASE EITHER 1" OVER ENTIRE | | | SITE OR 2.5" CRITERIA. EXFILTRATION TRENCH LENGTH WOULD | | | BE LOT MORE THAN YOU CALCULATED. | | | 2.PLEASE ADD IN DRAWING SET CITY OF WPB STANDARDS FOR | | | DUMPSTER ENCLOSURE, | | | SIDEWALK,DRIVEWAY,APPROACH,PARKING,HANDICAP PARKING, | | | ADA, STANDARDS. | | | 3 NEED POLLUTION PREVENTION PLAN DETAILS | | | 4 NEED UTILITY REVIEW FROM 45TH STREET | | | 5 PLEASE SHOW STORM WATER CATCH BASINS & OUTLETS AROUND | | | YOUR SITE | | | | | | PLEASE RESPOND EACH ITEM TO EXPEDITE PERMITTING | | | PROCESS. | | | | | | RASIKCHOKSHI |
|