| 2006-10-15 14:16:59 | ********* UNSAT2ND REVIEW *********** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH NEW NOTES DUE TO |
| | INFORMATION NOW SHOWN OR CHANGES MADE. |
| | |
| | |
| | 1) NOTE: NO, SAME NOTE . |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE FOLLOWING |
| | MININUM CODES SHALL BE SPECIFIED ON THE |
| | PLANS FOR DESIGN AND BUILDING. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| | 2002. |
| | |
| | 2) NOTE:NO, COULD NOT LOCATE ANY INFORMATION ON |
| | SUMMARY OR BREAK DOWN OFLOADS AND HOW THEY HAVE BEEN |
| | FIGURED OR DERIVED? PLEASE ALSO SEE COMMENT FOR SIGN |
| | CIRCUIT. PLEASE SEE BOTH ARE BEING SHOWN ON THE SAME |
| | CIRCUIT NOW ON PANEL "L" WHICH PANEL "M" STILL SHOWS |
| | THE CIRCUITING WHICH WAS DONE ON PREVIOUS PLANS( M-15) |
| | ?? PLEASE SEE ALL NOTES PERTAINIGN TO THESE ADJUST AND |
| | CORRELATE. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE SHOW WINDOW |
| | REQUIRED DEDICATED CIRCUITS MAY NOT BE |
| | SHARED AS/OR WITH THE REQUIRED SIGN |
| | CIRCUITS. PLEASE SHOW LOADS PER 220.12A |
| | ON CALCS FOR "WATTS" PER LINEAR FT. |
| | |
| | 3) NOTE:NO, PLEASE SEE NOTE ABOVE, ALSO PLEASE SEE |
| | 600.5, AS PERVIOUSLY NOTED FOR LOCATION(S) OF REQUIRED |
| | CIRCUIT. PLEASE SEE THE SAME 600.5 WHICH REFERENCES |
| | 220.3B6 FOR MIN VA REQUIRED FOR THIS. PLEASE SEE PANEL |
| | SCHEDULE EITHER "M" OR "L" EACH SHOWS A 4A LOAD?? HOW |
| | IS THIS POSSIBLE WHEN THE MIN VA IS REQUIRED TO BE |
| | FIGURED AT 1200VA.PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE REQUIRED |
| | DEDICATED SIGN CIRCUITS SHALL BE SIZED |
| | AND CIRCUITED PER 600.5 WHETHER OR NOT |
| | AN ELECTRICAL TYPE SIGN WILL BE |
| | INSTALLED. |
| | |
| | 4) NOTE: ? SEE NEW NOTES AS THIS NOTE WAS ADDED ON |
| | PANEL SCHEDULE FOR "PLUGMOLD"?? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 220.12B, TRACK LTS |
| | SHALL BE SHOWN IN CALCULATIONS . |
| | |
| | 5) NOTE:NO, SAME NOTE, ALONG WIHT NOTES ABOVE ABOUT |
| | SIGNS, SHOW WINDOWS ETC, PLEASE PROVIDE A LOAD SUMMARY |
| | ON HOW LOADS WERE DERIVED. SHOWING A CONNECTED AMERAGE |
| | LOAD DOES NOTPROVIDE INFORMATION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT LOAD |
| | CALCULATIONS SHALL BE SHOWN. RECEPTS |
| | WHEN KNOWN ARE TO BE SHOWN, LIGHTING |
| | LOADS SHALL BE SHOWN AND IF CONTINUOUS |
| | THESE SHALL BE IDENTIFIED WITH 125% FIG. |
| | PLEASE SEE CALCUALTIONS WILL BE REQUIRED |
| | EVEN IF NO DERATINGS ARE GOING TO BE |
| | DONE. PLEASE SEE THE LOADS ON PANELS NOW |
| | ARE NOT COMPLETE AT THIS TIME. |
| | 220.3,220.10,220.11,220.13,, |
| | 215.3,230.42 ETC. |
| | 215.5 |
| | |
| | 6) NOTE:NO, PLEASE SEE THESE ARE STILL BEING SHOWN |
| | WITH TWO SEPARATE LOADS, WHERE THE MECHANICAL PLANS |
| | STILL INDICATE BOTH OF THESE BEING SAME?? |
| | PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE LOADS AND OCP |
| | FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 |
| | ARE THE SAME , YET THE AMPERAGE IS NOT |
| | THE SAME AND THE OCP IS DIFFERENT? |
| | PLEASE SEE MECHANICAL PLANS AND |
| | CORRELATE. |
| | PLEASE BE SURE TO SEE 424.3B FOR 125% |
| | OCP MIN. |
| | PLEASE ADJUST AWG PER 310.16 |
| | |
| | 7) NOTE:NO, THIS IS UNCLEAR AT THIS TIME AS THE |
| | STAIRS AND MEZZ LEVELS ARE UNCLEAR IF THEY EVEN EXIST |
| | ANYMORE AS SHEETS ARE STILL BEING SUBMITTED SHOWING A |
| | MEZZ LEVEL, YET NO LIGHTING OR STAIRS ARE SHOWN?? |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW THE NORMAL AND |
| | EMERGENCY FT CANDLES FOR STAIRS. PLEASE |
| | SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH |
| | NOW REQUIRES 10FT CANDLES (108LUX) UNDER |
| | NORMAL AND 10.8 FT CANDLES (10.8) UNDER |
| | EM CONDITIONS. |
| | PLEASE SHOW THE PHOTO-METRICS FOR THE |
| | EGRESS PATHS TO THE PUBLIC RIGHT OF WAY |
| | AS REQUIRED. |
| | |
| | 8) NOTE: ? NO, ?PANEL HAS NOT MOVED AND ROOM |
| | DESIGNATION HAS BEEN REMOVED FROM PLANS ALL TOGETHER?? |
| | THE ROOM SHALL BE IDENTIFIED ON PLANS FOR USE AND |
| | OCCUPANCY. IF INDEED THIS IS GOING TO BE USED AS A |
| | STORAGE ROOM, PLEASE RELOCATE PANELS AS THIS IS A LIFE |
| | SAFETY ISSUE AND AT THE VERY LEAST A FIRE HAZARD TO THE |
| | OCCUPANTS AND PROPERTY DAMAGE POTENTIAL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LOCATION OF PANEL |
| | "L" SHALL NOT BE LOCATED IN STORAGE |
| | ROOM. |
| | PLEASE RELOCATE.110.26,408.7, 240.24 |
| | ETC. |
| | PLEASE ALSO SHOW SECTION #2 OF PANEL "L" |
| | ON PLANS. |
| | |
| | 9) NOTE: OK, HOWEVER DUE TO PLANS NOT BEING COMPLETE |
| | FOR CLEAR REVIEW, PLEASE SEE PLANS WHICH STILL INDICATE |
| | A MEZZ LEVEL IN SETS DO NOT CONTAIN SOME ITEMS |
| | IDENTIFIED TO BE ON FIXTURE SCHEDULE. FIXTURE FOR |
| | POSSIBLE STAIR AREA IS NTO SHOWN, PLEASE SEE OTHER |
| | NOTES FOR COORDINATION. |
| | |
| | ** PREIVOUS REVIEW NOTE ** |
| | PLEASE COMPLETE FIXTURE |
| | IDENTIFICATION ON PLANS. PLEASE SEE SOME |
| | ARE MISSING FIX DESIGNATIONS. |
| | PLEASE ALSO SEE SOME FIXTURES ON FIX |
| | SCHEDULE COULD NOT BE LOCATED ON PLANS? |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK, CIRCUITING WAS COMPLETED HOWEVER WILL BE |
| | REVISED BASED ON OTHER COMMENTS. |
| | |
| | 12) NOTE: OK, HOWEVER SEE ONE NEW NOTE AS "FYI". |
| | |
| | 13) NOTE: OK, HOWEVER PROVIDE A GROUNDING ELECTRODE |
| | ATTACHMENT DETAIL FOR A NEW BUILDING? PLEASE KNOW IT |
| | SEEMS THIS BUILDING IS EXISTING AND TO SHOW AN |
| | ATTACHMENT TO THE FOOTER STEELMAY NOT BE DESIRED. |
| | PLEASE KNOW ON AN EXISTING OLDER BLDG WHERE THE FOOTER |
| | STEEL IS NOT AVAILABLE, IT IS NOT REQUIRED TO CHIP |
| | OUT/EXPOSE THE EXISTING FOOTER STEEL (IF THERE IS ONE) |
| | AS THIS MAY AFFECT THE STRUCTURAL INTEGRITY OF THE |
| | EXSITING FOOTER AND HAVING TO SEAL THIS AREA BACKSO |
| | THAT MOISTURE AND SPALDING DOES NOT OCCUR. PLEASE ONLY |
| | INCLUDETHE LOCATIONS WHICH WILL BE AVAILABLE ETC PER |
| | 250.50 2002 NEC. CODES ARE NOTE REQUIRED TO BE ON |
| | DETAIL HOWEVER MAY. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW THE LOCATION OF |
| | THE ATTACHMENT OF THE GROUNDING |
| | ELECTRODE CONDUCTOR. |
| | 250.24B,250.6,215.5 |
| | |
| | 14) NOTE: OK, HOWEVER SEE 240.12 FOR SELECTIVE |
| | COORDINATION FOR DESIGNER TO VERIFY. THISNOTE WAS FOR |
| | AIC RATINGS.110.9 AND IS OK. |
| | |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE:NO/OK, OCCUPANT DEVICES HAVE BEEN USED AND |
| | ADDED TO ALMOST ALL LOCATIONS, HOWEVER AS THE MEZZ |
| | LEVEL IS NOT CLEAR THIS CAN NOT BE REVIEWED. PLEASE |
| | ALSO SEE NO LIGHTING POWER DENSITIES WERE LOCATED FOR |
| | MAX WATTAGE ALLOWED . 13-415.2.ABC.1 PLEASE ALSO |
| | SPECIFY THE MAX TIMES ON DEVICES CHOSEN. (TIMER TYPE |
| | 4HRS MAX, OS TYPE 30 MINS MAX). |
| | PLEASE SEE CIRCUITING OF EM/ EXT LTS WILL BE AFFECT AS |
| | SHOWN. MUST BE WIRED INTO BRANCH CIRCUIT AHEAD OF ANY |
| | CONTROL DEVICE. PLEASE INDICATE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THIS NOTE IS VERY |
| | IMPORTANT AND WILL REQUIRE MANY CHANGES |
| | IN THE ELECTRICAL LIGHTING SYSTEM AS |
| | SHOWN. |
| | PLEASE SEE FBC 2004 CHAPTER 13. PLEASE |
| | SEE THIS IS NEW IN THE 2004 CODE AND |
| | MANY CHANGES WERE MADE TO THE ELECTRICAL |
| | SECTION FROM THE 2001 FBC. THESE CHANGES |
| | BECAME FEDERALLY MANDATED IN JULY 04 FOR |
| | EACH STATE TO ADOPT THESE MIN |
| | REQUIREMENTS BY THE NEXT CODE CYCLE. |
| | |
| | **PLEASE SEE 13-101.1.3 THE ENERGY CODE |
| | COMPLIANCE FORM SHALL BE "C". |
| | PLEASE SEE 13-413.1.ABC.1, A WORST CASE |
| | VOLTAGE DROP CALCULATION WILL BE |
| | REQUIRED TO BE SHOWN ON PLANS FOR |
| | FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL |
| | OF WHICH REQUUIRES MANY ITEMS ON PLANS |
| | TO BE CHANGED. PLEASE INDICATE THE TYPE |
| | OF SYSTEM WHICH WILL BE USED, |
| | SCHEDULING, THE LOCATIONS OF THE |
| | REQUIRED OVER RIDE SWITCHES, THE |
| | LOCATIONS OF THE OCCUPANCY SENSORS(IF |
| | USED) AND PLEASE SEE THE REQUIREMENTS OF |
| | THE MULTIPLE FLOORS. ETC |
| | PLEASE BE SURE TO INCLUDE DEVICES FOR |
| | SEPARATE SPACES. |
| | |
| | |
| | 17) NOTE: OK. |
| | |
| | |
| | 18) NOTE:NO, THIS WAS NOT DONE,. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, BEFORE |
| | RESUBMITTING PLANS, PLEASE BE SURE TO |
| | COMPLETELY REMOVE ANY OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE "NEW" |
| | SHEETS INTO SETS FOR REVIEW AND |
| | STAMPING. THIS WILL HELP TO ALLEAVAITE |
| | DELAYS IN REVIEW OF SAID PROJECT. ONE |
| | COPY OF THE OLD/VOIDED REMOVED SHEETS |
| | SHOULD ACCOMPANY THE NEW SETS FOR |
| | REFERENCE. |
| | |
| | ** NEW NOTES ** |
| | |
| | 19) NOTE: PLEASE SEE ALL NOTES ABOVE WITH REPSETC TO |
| | MEZZ LEVEL AND COMPLETE PLANS ACCORDINGLY. |
| | |
| | 20) NOTE: ** THIS IS ONLY A NOTE: PLEASE SEE A 1/0 |
| | EQUIPMENT GROUNDING CONDUCTOR IS BEING SHOWN FROM MAIN |
| | TO PANEL "L". PLEASE SEE 250.122 FOR MIN REQUIRED. SIZE |
| | IS MUCH LARGER THAN NEEDED, HOWEVER MAY BE USED. PLEASE |
| | KNOW, IF SHOWN ON PLANS LIKE THIS, THEN THE 1/0 WILL BE |
| | REQUIRED OT BE INSTALLED. THIS IS FOR INFORMATIONAL |
| | PURPOSE ONLY AND DOES NOT NEED TO BE REVISED. |
| | |
| | 21) NOTE: PLEASE SEE A NOTE WAS ADDED TO PANEL WITH A |
| | DOUBLE "* *" NEXT TO CIRCUIT FOR PLUGMOLD WHICH NOTES |
| | LOADS ALL FIGURED PER 220.12B AND 150WATTS PER 2'?? |
| | PLEASE SEE 220.12B IS FOR TRACK LIGHTING AND MAY NOT BE |
| | USED FOR PLUGMOLD. PLEASE SEE PREVIOUS NOTE FOR LOAD |
| | CALCULATIONS AND REVISE. |
| | |
| | 22) NOTE: PLEASE SEE FOYER/ENTRANCE AREA SHALL CONTAIN |
| | AN EM LT AS THERE DOORS FROM OTHER AREAS WHICH DO |
| | SUPPLY THE NEEDED ILLUMINATION FOR REQUIRED EGRESS. |
| | PLEASE SEE NFPA-101 7.8, 7.9 |
| | |
| | 23) NOTE: PLEASE SEE COPY OF FLORIDA STATUES ATTACHED |
| | 553.80(2)(B) WITH RESPECTTO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | |
| | 24) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A |
| | WATER HEATER IN A STORAGE CLOSET.PLEASE RELOCATE. |
| | |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS/ DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |