| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) SHEET# 1 CODE DATA INDICATES A |
| | TYPE III BUILDING BUT NO DESIGNATION TO |
| | "A" OR "B". |
| | |
| | 4) COMPLIED. |
| | |
| | 5)2ND REQUEST, SHEET 1B INDICATES AS DEPICTED A 2" DROP |
| | FROM THE INTERIOR FINISH SLAB TO THE EXTERIOR OF THE |
| | BUILDING. |
| | SHEET# 1B INDICATES ELEVATIONS ON |
| | THE INTERIOR FINISH FLOOR OF 16.76'AND |
| | THE EXTERIOR ELEVATION OF 16.64'. |
| | 11-4.3.8 CHANGES IN LEVEL. |
| | CHANGES IN LEVELS ALONG AN ACCESSIBLE |
| | ROUTE SHALL COMPLY WITH SECTION 11-4.5.2 |
| | . IF AN ACCESSIBLE ROUTE HAS CHANGES IN |
| | LEVEL GREATER THAN ? INCH (13 MM), THEN |
| | A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM |
| | LIFT (AS PERMITTED IN SECTION 11-4.1.3 |
| | AND 11-4.1.6 ) SHALL BE PROVIDED THAT |
| | COMPLIES WITH SECTION 11-4.7 , 11-4.8 , |
| | 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN |
| | ACCESSIBLE ROUTE DOES NOT INCLUDE |
| | STAIRS, STEPS, OR ESCALATORS. SEE |
| | DEFINITION OF ?EGRESS, MEANS OF? IN |
| | SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND |
| | FIGURE 11-7 (D)]. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) SHEET 3, 4 AND SHEET 11 ALL DETECT A MEZANINE |
| | LEVEL. AS ASKED IN REVIEW COMMENT |
| | NUMBER 1 PLEASE REMOVE ALL OLD SHEETS FROM THE PERMIT |
| | PACKAGE. SHEET 11 ALSO NEEDS TO BE REMOVED. |
| | |
| | 11)COMPLIED, ONCE ALL REFRENCE TO MEZZANINE IS |
| | REMOVED FROM PLANS. |
| | |
| | 12) COMPLIED, ONCE ALL REFRENCE TO MEZZANINE |
| | |
| | 13) 2ND REQUEST, SHEET#3 DOESN'T PROVIDE ANY CUT |
| | SECTION THROUGH THE TENANT |
| | SEPERATION WALL PROVIDING A 1 HR TENANT SEPERATION. |
| | EITHER PROVIDE THE UL LISTING AND |
| | DESCRIPTION OF WALL OR TAKE THE PERSCRIPTIVE MEETHOD IN |
| | TABLE 720.1(2). |
| | |
| | 14) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE LEVEL |
| | ARE REMOVED. |
| | |
| | 17)) 1209.3 MECHANICAL APPLIANCES. |
| | ACCESS TO MECHANICAL APPLIANCES INSTALLED IN |
| | UNDER-FLOOR AREAS, IN ATTICS SPACES AND ON ROOFS OR |
| | ELEVATED STRUCTURES SHALL BE IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING MECHANICAL CODE. |
| | |
| | 18) COMPLIED ONCE ALL REFRENCES TO THE MEZZANINE ARE |
| | REMOVED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE ARE |
| | REMOVED. |
| | |
| | 23)COMPLIED. |
| | |
| | 24) COMPLIED. |
| | |
| | 25) 2ND REQUEST,) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 26)2ND REQUEST, UNTIL REVIEWD BY THE DESIGNED |
| | PROFESSIONAL |
| | AND SIGNED OFF ACCEPTED THIS COMMENT WILL REMAIN. FL |
| | BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FIXED WINDOWS |
| | B) MULLIONS |
| | C) GLAZED DOORS |
| | D) HOLLOW METAL DOORS SINGLE & PAIR |
| | E) ROOF ASSEMBLIES |
| | 1) FLAT ROOF INSULATION |
| | 2) MODIFIED SINGLE PLY |
| | 3) SLOPED ROOFING APPLICATION |
| | 4) ROOF TILE REPORT |
| | |
| | 27) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | ___ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS. |
| | |
| | _X_ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | _X_ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | _X_ NO SYSTEMS WERE SUBMITTED IN REPORT. MISSING |
| | SUBREPORTS LISTED PAGE9-18. |
| | NO SUBREPORT WAS HIGHLIGHTED.WITH THE REPORT |
| | SUBMITTED, THIS MAY BE A |
| | SITUATION: |
| | THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | _X_NO SUBSYSTEMS SUBMITTED, MAYBE A |
| | SITUATION. |
| | THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE |
| | OF HIP BOARD TO BE USED, ALSO |
| | INDICATE TYPE OF FASTENING. |
| | CLAY AND CONCRETE ROOF TILES SHALL BE |
| | FASTENED IN ACCORDANCE WITH SECTION 1609 |
| | OR IN ACCORDANCE WITH FRSA/RTI |
| | 07320/08/05 INSTALLATION MANUAL. |
| | |
| | 1507.3.8 APPLICATION. |
| | TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS |
| | OR RECOMMENDATIONS OF THE FRSA/RTI |
| | 07320/08/05. |
| | |
| | 28) COMPLIED. |
| | |
| | 29) PROVISO: TO BE CHECKED BY INSPECTOR BEFORE C.O.: |
| | 804.5.1 MINIMUM CRITICAL RADIANT FLUX . |
| | INTERIOR FLOOR FINISH IN VERTICAL EXITS, |
| | EXIT PASSAGEWAYS AND EXIT ACCESS |
| | CORRIDORS SHALL NOT BE LESS THAN CLASS I |
| | IN GROUPS I-2 AND I-3 AND NOT LESS THAN |
| | CLASS II IN GROUPS A, B, E, H, I- 4, M, |
| | R-1, R-2 AND S. IN ALL OTHER AREAS, THE |
| | INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, |
| | PART 1630). |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |