| Plan Review Notes For Permit 06050604 |
| Permit Number |
06050604 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-23 00:00:00 | *** DENIED *** | | | 1) AHU #1 SHOW SIZE OF MAIN RETURN AIR | | | DUCT TO 42"X24" R.A. GRILL IN MEZZANINE. | | | | | | 2) AHU #2 SHOW SIZE OF MAIN RETURN AIR | | | DUCT FROM AHU TO 12"X8" DUCTS. | | | | | | 3) AHU #3 SUPPLY AIR TO OFFICE CAN NOT | | | RETURN TO AHU #1, 10'X10" TRANSFER GRILL | | | DOES NOT OPEN TO AHU #3 ZONE. | | | | | | 4) A/C SUPPLY AIR DUCT AND RETURN AIR | | | TRANSFER GRILL GOING TO LOBBY ARE | | | PENETRATING A FIRE RATED WALL, AND | | | REQUIRE FIRE DAMPERS, PER 2004 FBC/M 607 | | | | | | 5) SEE BUILDING REVIEW NOTES #23 & #24. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|