| 2006-06-16 00:00:00 | 1. DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2. DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. |
| | |
| | 3. GASOLINE POWERED DEMOLITION EQUIPMENT |
| | SHALL NOT BE USED WITHOUT PROPER |
| | VENTILATION TO PREVENT CARBON MONOXIDE |
| | BUILD-UP OF VAPORS. |
| | |
| | 4. ADDITIONAL EXIT SIGNS APPEAR TO BE |
| | NEEDED TO DIRECT PERSONS TO EXITS THAT |
| | ARE BEYOND CORNERS AND ROOMS. |
| | |
| | 5. NEW STAIRS UP SHALL MEET MINIMUM CODE |
| | REQUIREMENTS. ANY HANDRAILS AND |
| | GUARDRAILS SHALL COMPLY WITH THE |
| | PRESCRIPTIVE STRENGTH REQUIREMENTS. |
| | |
| | 6. THE MEZZANINE IS TO BE USED FOR WHAT |
| | PURPOSES. PLEASE INDICATE THE PURPOSE ON |
| | THE PLANS. |
| | |
| | 7. PLEASE REVIEW DOORS SWINGS FOR |
| | RESTROOMS THAT OPEN ONTO THE CORRIDOR |
| | PROVIDING ACCESS TO THEM. |
| | |
| | 8. ENSURE THAT THE EXISTING ADDRESS |
| | DISPLAYEED ON PAGE 6A MEETS MINIMUM CODE |
| | REQUIREMENTS OF AT LEAST 6" HIGH WITH |
| | THE PROPER WIDTH STROKE. |
| | |
| | 9. FLOOR PLANS DOES NOT ILLUSTRATE ANY |
| | NEW OR EXISTING PORTABLE FIRE |
| | EXTINGUISHERS. PLEASE DISPLAY. |
| | |
| | 10. PLEASE INDICATE INTERIOR FINISH FOR |
| | WALLS AND CEILINGS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |