| 2006-06-10 00:00:00 | IN ELEC |
| | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING |
| | MININUM CODES SHALL BE SPECIFIED ON THE |
| | PLANS FOR DESIGN AND BUILDING. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| | 2002. |
| | |
| | 2) NOTE: PLEASE SEE THE SHOW WINDOW |
| | REQUIRED DEDICATED CIRCUITS MAY NOT BE |
| | SHARED AS/OR WITH THE REQUIRED SIGN |
| | CIRCUITS. PLEASE SHOW LOADS PER 220.12A |
| | ON CALCS FOR "WATTS" PER LINEAR FT. |
| | |
| | 3) NOTE: PLEASE SEE THE REQUIRED |
| | DEDICATED SIGN CIRCUITS SHALL BE SIZED |
| | AND CIRCUITED PER 600.5 WHETHER OR NOT |
| | AN ELECTRICAL TYPE SIGN WILL BE |
| | INSTALLED. |
| | |
| | 4) NOTE: PLEASE SEE 220.12B, TRACK LTS |
| | SHALL BE SHOWN IN CALCULATIONS . |
| | |
| | 5) NOTE: PLEASE SEE THAT LOAD |
| | CALCULATIONS SHALL BE SHOWN. RECEPTS |
| | WHEN KNOWN ARE TO BE SHOWN, LIGHTING |
| | LOADS SHALL BE SHOWN AND IF CONTINUOUS |
| | THESE SHALL BE IDENTIFIED WITH 125% FIG. |
| | PLEASE SEE CALCUALTIONS WILL BE REQUIRED |
| | EVEN IF NO DERATINGS ARE GOING TO BE |
| | DONE. PLEASE SEE THE LOADS ON PANELS NOW |
| | ARE NOT COMPLETE AT THIS TIME. |
| | 220.3,220.10,220.11,220.13,, |
| | 215.3,230.42 ETC. |
| | 215.5 |
| | |
| | 6) NOTE: PLEASE CORRELATE LOADS AND OCP |
| | FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 |
| | ARE THE SAME , YET THE AMPERAGE IS NOT |
| | THE SAME AND THE OCP IS DIFFERENT? |
| | PLEASE SEE MECHANICAL PLANS AND |
| | CORRELATE. |
| | PLEASE BE SURE TO SEE 424.3B FOR 125% |
| | OCP MIN. |
| | PLEASE ADJUST AWG PER 310.16 |
| | |
| | 7) NOTE: PLEASE SHOW THE NORMAL AND |
| | EMERGENCY FT CANDLES FOR STAIRS. PLEASE |
| | SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH |
| | NOW REQUIRES 10FT CANDLES (108LUX) UNDER |
| | NORMAL AND 10.8 FT CANDLES (10.8) UNDER |
| | EM CONDITIONS. |
| | PLEASE SHOW THE PHOTO-METRICS FOR THE |
| | EGRESS PATHS TO THE PUBLIC RIGHT OF WAY |
| | AS REQUIRED. |
| | |
| | 8) NOTE: PLEASE SEE LOCATION OF PANEL |
| | "L" SHALL NOT BE LOCATED IN STORAGE |
| | ROOM. |
| | PLEASE RELOCATE.110.26,408.7, 240.24 |
| | ETC. |
| | PLEASE ALSO SHOW SECTION #2 OF PANEL "L" |
| | ON PLANS. |
| | |
| | 9) NOTE: PLEASE COMPLETE FIXTURE |
| | IDENTIFICATION ON PLANS. PLEASE SEE SOME |
| | ARE MISSING FIX DESIGNATIONS. |
| | PLEASE ALSO SEE SOME FIXTURES ON FIX |
| | SCHEDULE COULD NOT BE LOCATED ON PLANS? |
| | |
| | 10) NOTE: PLEASE IDENTIFY ALL FIXTURES |
| | WHICH ARE EM TYPE, WITH THE REQUIRED |
| | NOTED BATTERY BACK UP. |
| | 215.5 |
| | |
| | 11) NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS. PLEASE BE SURE TO SEE 700.12E |
| | FOR EM/EXT LTS WHICH ARE REQUIRED TO BE |
| | CIRCUITED TO THE NORMAL BRANCH CIRCUIT |
| | IN THE AREA IN WHICH THESE FIXTURES ARE |
| | LOCATED. |
| | |
| | 12) NOTE: PLEASE COMPLETE RISER DIAGRAM. |
| | PLEASE INCLUDE ALL SEC'S ON RISER FROM |
| | METER TO GUTTER AND FROM GUTTER TO EACH |
| | MAIN(S). |
| | 310.16,215.5 |
| | |
| | 13) NOTE: PLEASE SHOW THE LOCATION OF |
| | THE ATTACHMENT OF THE GROUNDING |
| | ELECTRODE CONDUCTOR. |
| | 250.24B,250.6,215.5 |
| | |
| | 14) NOTE: PLEASE INDICATE THE AIC |
| | RATINGS FOR ALL SERVICE EQUIPMENT PER |
| | 110.9, 215.5 |
| | THIS IS SHOWN FOR PANELS, BUT NOT FOR |
| | MAINS?? |
| | |
| | 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | FOR ALL CIRCUITS. PLEASE KNOW, THE AREA, |
| | ROOM, IDENTIFICATION OF EACH CIRCUIT IS |
| | REQUIRED. IE: CONFERENCE RM RECEPTS, |
| | OFFICE #2 RECEPTS, BREAK RM RECEPTS,, |
| | ETC ETC. |
| | PLEASE KNOW, GENERAL "RECEPTS" OR |
| | "LIGHTS" ARE NO LONGER ACCEPTABLE.408.4, |
| | 215.5 |
| | ** PLEASE KNOW, IT IS KNOWN AND COMMON |
| | THAT THESE WILL CHANGE DURING THE |
| | CONSTRUCTION AND WILL BE REQUIED TO BE |
| | REVISED ALONG WITH ANY OTHER CHANGES AT |
| | A LATER DATE. THIS IS HOWEVER REQ'D AT |
| | THIS TIME. PLEASE BE SURE ALL AREA AND |
| | ROOM DESIGNATIONS ARE ON PLANS. |
| | |
| | 16) NOTE: PLEASE SEE THIS NOTE IS VERY |
| | IMPORTANT AND WILL REQUIRE MANY CHANGES |
| | IN THE ELECTRICAL LIGHTING SYSTEM AS |
| | SHOWN. |
| | PLEASE SEE FBC 2004 CHAPTER 13. PLEASE |
| | SEE THIS IS NEW IN THE 2004 CODE AND |
| | MANY CHANGES WERE MADE TO THE ELECTRICAL |
| | SECTION FROM THE 2001 FBC. THESE CHANGES |
| | BECAME FEDERALLY MANDATED IN JULY 04 FOR |
| | EACH STATE TO ADOPT THESE MIN |
| | REQUIREMENTS BY THE NEXT CODE CYCLE. |
| | |
| | **PLEASE SEE 13-101.1.3 THE ENERGY CODE |
| | COMPLIANCE FORM SHALL BE "C". |
| | PLEASE SEE 13-413.1.ABC.1, A WORST CASE |
| | VOLTAGE DROP CALCULATION WILL BE |
| | REQUIRED TO BE SHOWN ON PLANS FOR |
| | FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL |
| | OF WHICH REQUUIRES MANY ITEMS ON PLANS |
| | TO BE CHANGED. PLEASE INDICATE THE TYPE |
| | OF SYSTEM WHICH WILL BE USED, |
| | SCHEDULING, THE LOCATIONS OF THE |
| | REQUIRED OVER RIDE SWITCHES, THE |
| | LOCATIONS OF THE OCCUPANCY SENSORS(IF |
| | USED) AND PLEASE SEE THE REQUIREMENTS OF |
| | THE MULTIPLE FLOORS. ETC |
| | PLEASE BE SURE TO INCLUDE DEVICES FOR |
| | SEPARATE SPACES. |
| | |
| | |
| | 17) NOTE: PLEASE SEE THIS COMMENT IS NOT |
| | FOR ELECTRICAL ENGINEER. |
| | PLEASE SEE ALL COPIES OF PLANS DONE BY |
| | AN ENGINEER IS REQUIRED TO CONTAIN AND |
| | ORIGINAL SIGNATURE AND SEAL AND DATE. |
| | PLEASE SEE DRAINAGE CALCUALTIONS WHICH |
| | ARE "PHOTO-COPIES" OF SIGNED AND SEALED |
| | SHEETS. THIS IS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.025 WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER |
| | ENGINEERING/CIVIL REVIEWER. |
| | |
| | |
| | 18) NOTE: PLEASE KNOW, BEFORE |
| | RESUBMITTING PLANS, PLEASE BE SURE TO |
| | COMPLETELY REMOVE ANY OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT THE "NEW" |
| | SHEETS INTO SETS FOR REVIEW AND |
| | STAMPING. THIS WILL HELP TO ALLEAVAITE |
| | DELAYS IN REVIEW OF SAID PROJECT. ONE |
| | COPY OF THE OLD/VOIDED REMOVED SHEETS |
| | SHOULD ACCOMPANY THE NEW SETS FOR |
| | REFERENCE. |
| | |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS/ DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |