| Plan Review Notes For Permit 06050593 |
| Permit Number |
06050593 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-01-03 08:29:04 | *** DENIED *** | | | 1) AS NOTED IN LAST TWO REVIEWS 6-7-06 AND 9-12-06, | | | ENERGY CALCULATIONS MAY NOT BE ON FORM 600C-01 AS THE | | | ADDITION IS OVER 600 SQUARE FEET SEE PLANS. THE ENERGY | | | CALCULATIONS WILL NEED TO BE ON FORM 600A-04 (2004), | | | PER FBC 13-600.3.A . | | | | | | 2) A/C DUCT DESIGN WILL NOT WORK AS DRAWING ON | | | MECHANICAL PLANS, PLEASE CORRECT. | | | | | | 3) NEED TO SHOW THE CFM'S AT EACH SUPPLY AIR GRILL. | | | | | | 4)SEE ATTACHED NOTICE FS 553.80(2)(B) | | | REGARDING FOUR TIMES THE FEE (IN REFERENCE TO NOTE | | | #1). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|