| 2007-02-21 08:33:10 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEWS: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE SEPARATE GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****OK |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | ****OK |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ****RESPONSE NOTED, BUT THE BTU INFORMATION SUBMITTED |
| | IS CONFLICTING FROM ONE PAGE TO THE OTHER. THE NEXT TO |
| | LAST SHEET INDICATES THE BTU LOAD TO BE 905,000 BTU'S, |
| | BUT THE FINAL PAGE INDICATES FUEL CONSUMPTION TO BE |
| | 4200 CFH, (4,536,000 BTU'S). PLEASE CLARIFY AS THIS IS |
| | A LARGE DISCREPENCY. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****OK |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ****NOT SUBMITTED. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****OK |
| | |
| | 7. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ****OK |
| | |
| | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | MANUFACTURES INSTALLATION INSTRUCTIONS |
| | REQUIRE TO SHOW MINIMUM CLEARANCES FROM |
| | ALL STRUCTURES. |
| | ****OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |