Text |
| 2006-05-16 00:00:00 | 1) THE PRODUCT APPROVAL FOR THE FLAT |
| | ROOF IS MISSING FROM PACKAGE. SUBMIT AN |
| | APPROVED AND UPDATED PRODUCT FOR THE |
| | FLAT ROOF.MAKE SURE THE SYSTEM WHICH |
| | WILL BE USED IS HI-LIGHTED OR CIRCLED. |
| | READ THE GENERAL LIMITATIONS FOR THE |
| | APPROVED ASSEMBY WHICH MAY OR MAY-NOT |
| | REQUIRE CALCULATIONS FROM A REGISTERED |
| | PROFESSIONAL ENGINEER/ARCHITECT OR |
| | ROOFING CONSULTANT. |
| | |
| | 2) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | ___ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | ___ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | ___ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | ___THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |