| Plan Review Notes For Permit 06050571 |
| Permit Number |
06050571 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-19 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLAN REVIEW FOR A GAS PERMIT: | | | | | | 1. TYPE OF GAS, (LP OR NATURAL) THIS HAS | | | TO BE INDICATED ON THE DRAWINGS. | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4).(EXISTING | | | SYSTEM MUST BE INDICATED ON DRAWING AND | | | INDICATE THE POINT OF TIE IN FOR FIRE | | | PLACE) | | | 4. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | | | | |
|