| 2006-06-10 00:00:00 | ***** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE PROVIDE A MORE DETAILED |
| | LAYOUT/OVERVIEW OF EQUIPMENT LOCATIONS. |
| | SURVEY SEEMS TO LOCATION OF THE NEW CT |
| | AND ATS, BUT THE DISCONNECT ON RISER |
| | COULD NOT BE SEEN. |
| | PLEASE PROVIDE PERHAPS A "BLOW-UP" OF |
| | THIS AREA. |
| | THIS IS NEEDED TO VERIFY THE GROUPING OF |
| | MAINS AS REQUIRED PER 230.72,225.34 |
| | |
| | 2) NOTE: PLEASE SPECIFY ON RISER THE AIC |
| | RATINGS FOR ALL NEW SERVICE EQUIPMENT. |
| | PLEASE SEE THE DISC FOR THE FEEDERS |
| | COMING FROM GEN SHALL BE RATED FOR THE |
| | VAILABLE FAULT CURRENT FROM GEN AND THE |
| | NEW SE RATED ATS SHALL ALSO BE RATED FOR |
| | THE AVAILABLE FROM FPL. |
| | 110.9,702.5 |
| | |
| | 3) NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" SHALL NOT BE |
| | INSTALLED BEFORE TH FIRST MEANS OF |
| | DISCONNECT. PER 250.6,250.24B |
| | |
| | 4) NOTE: PLEASE SEE THE MAIN AT THE NEW |
| | SE RATE ATS NEEDS TO BE NOTED AND |
| | VERIFIED ANS CONTAINING A MANUAL MEANS |
| | OF DICONNECT, RATED FOR THE LOAD SERVED |
| | AND ON THE OUTSIDE OF THE EQUIPEMNT NOT |
| | EXPOSING ANY LIVE PARTS INORDER TO |
| | SHUT DOWN POWER. |
| | PLEASE SEE 230.76,230.79, 110.27 |
| | THIS SEEMS TO BE THE CASE, HOWEVER IT IS |
| | NOT CLEAR AT THIS TIME BY THE SPECS AND |
| | RISER SUBMITTED. |
| | |
| | 5) NOTE: PLEASE KNOW, IF USING THE |
| | ONE-YEAR FPL USEAGE FOR SIZING THE GEN, |
| | THEN THIS SHALL CONTAIN A STATEMENT FROM |
| | THE RESPONSIBLE DESIGNER WHICH STATED |
| | THE AVG OVERALL KW USAGE AND THE RATING |
| | FOR NEW GEN WITH THE PRINTED NAME AND |
| | SIGNATURE ON THE LOAD SHEETS PROVIDED |
| | FROM FPL. |
| | |
| | 6) NOTE: PLEASE SEE PLUMB REVIEW |
| | COMMENTS AS THE VALUE STATED ON |
| | APPLIACTION SHALL INCLUDE ALL LABOR AND |
| | MATERIALS WHICH OULD INCLUDE THE COST OF |
| | THE PROPOSED TANKS. |
| | FBC 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE FIRE REVIEW COMMENTS AS |
| | THESE MAY HAVE AN AFFECT ON |
| | DESIGN/INSTALLATION. |
| | |
| | |
| | ** PLEASE KNOW, THIS ADDRESS IS NOT |
| | LOCATED IN A FLOOD ZONE. AN ELEVATION |
| | CERTIFICATE WILL NOT BE REQUIRED BEFORE |
| | FINAL. |
| | |
| | PLEASE SUBMIT THE ABOVE CORRECTIONS AND |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |