| 2006-05-31 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)CODE COMPLIANCE CANNOT BE | | | DETERMINED DUE TO CONFLICTING | | | INFORMATION IN THE PERMIT PACKAGE. | | | | | | YOU HAVE DECLARED WIND PRESSURES USING | | | SOFTWARE; THESE PRESSURES APPEAR | | | COMPLIANT.ON THE PRODUCT APPROVAL, YOU | | | HAVE CIRCLED -31.2, WHICH IS TOO LOW FOR | | | 140MPH. | | | | | | YOU HAVE CIRCLED THE NUMBER -31.2 IN | | | SEVERAL DIFFERENT PLACES, SHOWING TWO | | | DIFFERENT EDGE DISTANCES AND TWO | | | DIFFERENT FASTENERS. | | | | | | THE SPACING OF 12"/12" SPECIFIED ON THE | | | SCHEDULE IS NOT COMPLIANT FOR ALL | | | OPENINGS.SEE THE ANCHOR SPACING | | | REQUIRED FOR -47.2. | | | |
|