| 2006-09-26 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) NO PRODUCT APPROVALS WERE SUBMITTED |
| | FOR THE SECTIONAL GARAGE DOORS #'S 103, |
| | 104 AND 106 |
| | |
| | 2) CECO SWINGING DOORS ARE HOLLOW METAL |
| | FOR #'S 100 AND 101 AND DRAWING STATES |
| | WOOD PLEASE CORRECT |
| | |
| | 3) DRAWINGS SPECIFY IMPACT RESISTANT |
| | WINDOWS AND THE PRODUCT APPROVALS THAT |
| | ARE SUBMITTED ARE FOR NON IMPACT, PLEASE |
| | CORRECT (FLORIDA COVER IS THE SAME) |
| | |
| | 4) PROVIDE TYPE OF ROOF COVERING AND |
| | PRODUCT APPROVAL FOR BREEZEWAY |
| | |
| | 5) ONLY ONE COPY OF ROOFING PRODUCT |
| | APPROVAL WAS SUBMITTED. PLEASE CONFIRM |
| | THIS TYPE OF ROOF COVERING IS TO BE USED |
| | AS IT IS FASTENED THROUGH THE MEMBRANE |
| | AND INSULATION INTO DECK. THE RAS 117 |
| | CALCULATIONS DO NOT MEET THE REQUIRED |
| | AMOUNT OF FASTENERS (SEE PAGE 5 OF NOA) |
| | FASTENERS AND PLATES ARE MECHANICALLY |
| | ATTACHED SPACED AT 6" ON CENTER TO MEET |
| | THE -45 PSF |
| | |
| | 6) PLEASE REMOVE ANY ROOM DESIGNATIONS |
| | AND WALLS FROM DRAWINGS AS THE CITY CODE |
| | STATES THAT THE GARAGE FLOOR IS EXEMPT |
| | FROM BEING 6" ABOVE FLOOD ELEVATION WHEN |
| | ITS SOLE USE IS FOR VEHICLE PARKING |
| | |
| | 7) PLEASE REMOVE ALL NON USED PRODUCT |
| | APPROVALS FROM THE SUBMITTAL. ONLY RE |
| | SUBMIT 2 COMPLETE SETS OF PRODUCT |
| | APPROVALS AND DRAWINGS ALONG WITH THE |
| | OLD PAGES THAT ARE CHANGED AND THE OLD |
| | PAGES WITH THE IMPACT FEE STAMPS |
| | |
| | 8) PER 713.13(2) F.S. |
| | IF THE IMPROVEMENT DESCRIBED IN THE NOC |
| | HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING THE NOTICE IS VOID |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |