| Plan Review Notes For Permit 06050515 |
| Permit Number |
06050515 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-17 00:00:00 | | | | DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FORCODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE 1/0 FEEDER TO THE "200 AMP ELEC. | | | PANEL MLO SN" IS RATED FOF 175 AMPS PER | | | 310.15(B)(6). INDICATE THE OCP IN THE | | | METER/MAIN COMBO FOR THIS FEEDER. 200 | | | AMP IS TOO LARGE. | | | | | | 2} INDICATE THE AIC RATING AS CALCULATED | | | FOR THE FAULT CURRENT FROM THE | | | TRANSFORMER TO THE EQUIPMENT PER 110.9 & | | | 10. | | | | | | 3} PLEASE SEE THE FOLLOWING CIRCUITS IN | | | THE PANEL ARE INCORRECT: | | | | | | A) 8&9- SMALL APPLIANCE@ 1500 EACH PER | | | 210.11(C)(3)=300VA. | | | | | | B) 12&14-#12 WIRE ON A 30 AMP OCP, | | | 310.16. | | | | | | C) 17&19-AHU @ 10K DOES NOT CORRELATE | | | WITH SHEET #9 INDICATING 5K. | | | | | | 4} PLACE THE SERVICE EQUIPMENT AT THE | | | PROPOSED LOCATION ON THE PLAN. | | | | | | 5} PLEASE SEE A RECEPTACLE FOR A/C | | | EQUIPMENT PER 210.63 IS REQUIRED FOR THE | | | COMPRESSOR. | | | | | | 6} THE ENGINEERS CERTIFICATE OF | | | AUTHORIZATION NUMBER MUST BE INCLUDED IN | | | THE TITLE BLOCK PER 61G15-002 (2), FAC. | | | ALL SHEETS . | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|