| Plan Review Notes For Permit 06050493 |
| Permit Number |
06050493 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-05 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 SEC. 424.2 SWIMMING | | | POOLS OR FBC-2004 RESIDENTIAL SEC.R4101 | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FROM PLUMBING PLAN REVIEW FOR A PERMIT: | | | | | | 1) FBC-2004 SEC. 424.2.6.6.5, OR | | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | | NOT GREATER THAN 12" BELOW THE MINIMUM | | | OPER- ATING WATER LEVEL OR AS AN | | | ATTACHMENT TO THE SKIMMER.(MANUFACTURER | | | CUT SHEETS REQUIRED OR ADD MAKE AND | | | MODEL NUMBER TO PRINTS) | | | 2) FBC-2004 SEC. 424.6.6 OR FBC-2004 | | | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. PLEASE | | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | | OF THE1-1/2" PVC VENT PIPE, FROM WHERE | | | IT STARTS TO WHERE IT ENDS UP, COMPLYING | | | WITH THE THREE SECOND RELEASE. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | | | | |
|