| Plan Review Notes For Permit 06050482 |
| Permit Number |
06050482 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-31 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06050482 | | | ADD: 1101 S FLAGLER DR BLDG "I" | | | CONT: RALPH DELLA-PIETRA, INC. | | | TEL: (561)745-8555 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 2) DISCREPANCY PERMIT APPLICATION | | | DESCRIBES THE REMOVAL OF 5/8" CDX | | | PLYWOOD AND ADDING 5/8" PLYWAOOD | | | SHEATHING WHEREAS THE PLANS ONLY | | | INDICATE "REMOVAL" OF PLYWOOD, NO | | | MENTION OF REPLACEMENT, WHAT ABOUT SHEER | | | WALLS? | | | | | | 3) SHEET A-3 IS MISSING INFORMATION ON | | | WIRE LATH: | | | 2510.3 INSTALLATION. | | | INSTALLATION OF THESE MATERIALS SHALL BE | | | IN COMPLIANCE WITH ASTM C 926 AND ASTM C | | | 1063. | | | A) TYPE OF LATH,& WEIGHT | | | B) FASTENER& SPACING | | | | | | 4) DETAIL @ WINDOWS & DOORS. | | | | | | 5) A-3 DISCREPANCY, SOFFITS THERE ARE | | | (2) NOTES ONE FOR 3/8" EXT GRADE PLYWOOD | | | FOR SOFFIT THE OTHER IS TO REMOVE AND | | | STUCCO SOFFIT. PROVIDE TYPE OF LATH FOR | | | SOFFITS, (24" C/C)? | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | |
|