| Date |
Text |
| 2006-12-10 09:08:43 | ******* UNSAT5TH REVIEW******** |
| | |
| | ** PLEASE KNOW THIS IS THE FIFTH TIME PLANS HAVE BEEN |
| | REVIEWED, HOWEVER ONLY THE SECOND TIME ACTUALLY UNDER |
| | PERMIT APPLICATION. PLEASE SEE NOTE BELOW WITH RESPECT |
| | TO FLORIDA STATUTES WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | PLEASE SEE LOAD SHOWN ON TRANSFORMER PLACES LOAD AT |
| | 44.97KVA ON PREVIOUS PLANS AND NOW 47.92 WHICH |
| | INDICATES LOADS EXCEEDING TRANSFORMER AS SHOWN. PLEASE |
| | SEE ABOVE NOTES, AS CONTINUOUS LOADS WILL PLACE THIS |
| | LOAD OVER RATING OF SAID 45KVA UNIT. |
| | PLEASE CLARIFY WHAT APPEARS TO BE ADDITIONAL LOAD ON |
| | "PA"? HOW, ARE THESE LOADS DIFFERENT OF THAT ON "DP"? |
| | PLEASE SHOW COMPLETE LOAD CALCULATIONS PER ABOVE AND |
| | 220.3, 220.10, 220.11, 220.13 |
| | ETC. AND 215.3, 230.42 ETC |
| | |
| | 2) NOTE:PREVIOUS NOTES BELOW WHICH HAVE NOT BEEN |
| | ADDRESSED. PLEASE SEE RESPONSE LETTER MENTIONS |
| | OCCUPANCY SENSORS WERE ADDED HOWEVER THIS DOES NOT |
| | COMPLETE COMMENTS FROM PREVIOUS REVIEWS. |
| | PLEASE SEE MISSING SCHEDULING. |
| | PLEASE SEE MAXIMUM TIMES FOR DEVICES. |
| | PLEASE SEE TIME CLOCK STILL SHOWN, HOWEVER NO |
| | CIRCUITING ETC. |
| | PLEASE SEE NO LIGHTING POWER DENSITIES? |
| | PLEASE KNOW BASED ON INFORMATION AS SUBMITTED A |
| | COMPLETE REVIEW CAN NOT BE DONE. |
| | ** PLEASE SEE 700.12E AS ALL EM/ EXT LTS SHALL BE |
| | INDICATED AHEAD OF ANY OC/TIMER TYPE DEVIE. |
| | |
| | ** PREVIOUS REVIEW NOTES FROM THE TWO PREVIOUS REVIEWS |
| | ALONE. ** |
| | NO, PLEASE SEE CONTROLS FOR ALL SEPARATE SPACES DO NOT |
| | SEEM TO BE INDICATED.(BATHRM) PLEASE SEE "S" ARE BEING |
| | NOTED IN RESPONSE LTR AND SHOWN AS OC , HOWEVER IF |
| | THESE DEVICES ARE LOCATED BEHIND WALL WHICH SEPARATES |
| | STORAGE/BACK AREA FROM STORE SALES AREAS, HOW WOULD |
| | THESE OCSENSOR TYPE SWITCHES BE EFFECTIVE. PLEASE |
| | INDICATE THE NORMAL SCHEDULING TIME OF DAY. PLEASE |
| | CLARIFY WHERE THE MAX TIMES PERMITTED ON THE DEVICES AS |
| | CHOSEN IS LOCATED ON PLANS? (OC TYPE 30MINS) (TIMER |
| | TYPE 4HRS MAX). |
| | PLEASE SEE MISSING THE PERFORMANCE CALCULATIONS PER |
| | 13-415.2, 13-415.2.ABC.1, TABLES, 415.2.C.1, 415.2.B.1 |
| | PLEASE SHOW A BREAK DOWN ON MAX LIGHTING POWER |
| | DENSITIES. |
| | |
| | ** PREVIOUS REVIEW NOTES** |
| | PLEASE SEE FBC 2004 CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2, AND .1.3. |
| | PLEASE SEE SPACE IS IN A BUILDING GREATER THAN 5000 SQ |
| | FT AND CONTROLS FOR LIGHTING WILL BE REQUIRED (SHOWN), |
| | HOWEVER PLEASE SEE .1.2, AND .1.3 AS CONTROLS FOR |
| | SEPARATE SPACES WITH FLR TO CEILING PARTITIONS ARE |
| | REQUIRED. PLEASE SEE PERMITTED TYPE OF DEVICES AS |
| | "TIMER" TYPE OVER RIDES ARE ONLY PERMITTED TO OVER RIDE |
| | NORMAL SCHEDULING A MAX OF 4HRS. PLEASE SEE ANY |
| | OCCUPANCY SENSOR(S) TYPE DEVICES SHALL ONLY PERMIT A |
| | MAX OF 30 MINS. PLEASE SHOW LOCATION OF THESE OVER |
| | RIDES DEVICES AND PLEASE SEE THESE ARE REQUIRED AT THE |
| | POINT OF ENTRANCE INTO SPACE SO THE OCCUPANT CAN |
| | VISUALLY SEE LTS BEING CONTROLLED. PLEASE SEE EXCEPTION |
| | FOR OCC SENSORS. PLEASE SEE BATH R, STOCK RM ETC,,, |
| | IT IS NOTED BY THIS OFFICE THAT A TIME CLOCK IS BEING |
| | PROVIDED, HOWEVER PLEASE SEE ABOVE FOR OTHER |
| | REQUIREMENTS. |
| | |
| | 3) NOTE: PLEASE SEE NOTE #1, BASED ON THE UNCERTAINTY |
| | OF LOADS ON THE TRANSFORMER, THE RISER MAY BE NEEDING |
| | TO BE REVISED AS STATED ON PREVIOUS REVIEWS. THE |
| | TRANSFORMER WAS CHANGED ONCE TO 75 KVA WHICH WAS OK, |
| | HOWEVER NOT ALL AREAS OF PLANS WERE REVISED TO |
| | CORRELATE WITH THIS. |
| | |
| | 4) NOTE:PLEASE SEE AS NOTED ON PREVIOUS REVIEWS, DO |
| | NOT USE THE "RUBBER STAMP" WHICH CONTAINS THE WORDING |
| | OF "CERTIFICATE" FOR SEAL. IT IS NOTED THAT A RAISED |
| | SEAL IS BEING PLACED OVER THIS RUBBER STAMP. |
| | THE RUBBER STAMP FOR USE IN THE STATE OF FLORIDA IS NOT |
| | PERMITTED AND SEEING THAT IT WORDING IS NO LONGER |
| | VALID, PLEASE DO NOT USE. |
| | FAC 61G15-23.001, FS 471.025 |
| | AS PREVIOUSLY NOTED. |
| | |
| | 5) NOTE: PLEASE SEE AS NOTED ABOVE, PLEASE SEE FLORIDA |
| | STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE AS THIS IS ONLY THE 2ND REVIEW UNDER PERMIT |
| | APPLICATION THE FEE AS MENTIONED IN THE ATTACHED SHEET |
| | IS NOT ASSESSED, HOWEVER IF PLANS COME BACK WITH ANY OF |
| | THE ITEMS IN THE NOTES ABOVE NOT ADDRESSED, A 4X FEE IS |
| | ASSESSED TO THE DESIGN PROFESSIONAL BASED ON THE |
| | PORTION OF BASE PERMIT FEE ATTRIBUTED TO PLAN REVIEW. |
| | *** PLEASE KNOW AT THIS TIME, ONE SET OF ME PLANS WILL |
| | BE RETAINED AND HELD IN FILE FOR POSSIBLE REVIEW BY THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS AND LEGAL |
| | COUNSEL TO THE BOARD. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |