Plan Review Notes
Plan Review Notes For Permit 06050449
Permit Number 06050449
Review Stop E
Sequence Number 5
Notes
Date Text
2006-12-10 09:08:43******* UNSAT5TH REVIEW********
  
 ** PLEASE KNOW THIS IS THE FIFTH TIME PLANS HAVE BEEN
 REVIEWED, HOWEVER ONLY THE SECOND TIME ACTUALLY UNDER
 PERMIT APPLICATION. PLEASE SEE NOTE BELOW WITH RESPECT
 TO FLORIDA STATUTES WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
  
  
 1) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 PLEASE SEE LOAD SHOWN ON TRANSFORMER PLACES LOAD AT
 44.97KVA ON PREVIOUS PLANS AND NOW 47.92 WHICH
 INDICATES LOADS EXCEEDING TRANSFORMER AS SHOWN. PLEASE
 SEE ABOVE NOTES, AS CONTINUOUS LOADS WILL PLACE THIS
 LOAD OVER RATING OF SAID 45KVA UNIT.
 PLEASE CLARIFY WHAT APPEARS TO BE ADDITIONAL LOAD ON
 "PA"? HOW, ARE THESE LOADS DIFFERENT OF THAT ON "DP"?
 PLEASE SHOW COMPLETE LOAD CALCULATIONS PER ABOVE AND
 220.3, 220.10, 220.11, 220.13
 ETC. AND 215.3, 230.42 ETC
  
 2) NOTE:PREVIOUS NOTES BELOW WHICH HAVE NOT BEEN
 ADDRESSED. PLEASE SEE RESPONSE LETTER MENTIONS
 OCCUPANCY SENSORS WERE ADDED HOWEVER THIS DOES NOT
 COMPLETE COMMENTS FROM PREVIOUS REVIEWS.
 PLEASE SEE MISSING SCHEDULING.
 PLEASE SEE MAXIMUM TIMES FOR DEVICES.
 PLEASE SEE TIME CLOCK STILL SHOWN, HOWEVER NO
 CIRCUITING ETC.
 PLEASE SEE NO LIGHTING POWER DENSITIES?
 PLEASE KNOW BASED ON INFORMATION AS SUBMITTED A
 COMPLETE REVIEW CAN NOT BE DONE.
 ** PLEASE SEE 700.12E AS ALL EM/ EXT LTS SHALL BE
 INDICATED AHEAD OF ANY OC/TIMER TYPE DEVIE.
  
 ** PREVIOUS REVIEW NOTES FROM THE TWO PREVIOUS REVIEWS
 ALONE. **
 NO, PLEASE SEE CONTROLS FOR ALL SEPARATE SPACES DO NOT
 SEEM TO BE INDICATED.(BATHRM) PLEASE SEE "S" ARE BEING
 NOTED IN RESPONSE LTR AND SHOWN AS OC , HOWEVER IF
 THESE DEVICES ARE LOCATED BEHIND WALL WHICH SEPARATES
 STORAGE/BACK AREA FROM STORE SALES AREAS, HOW WOULD
 THESE OCSENSOR TYPE SWITCHES BE EFFECTIVE. PLEASE
 INDICATE THE NORMAL SCHEDULING TIME OF DAY. PLEASE
 CLARIFY WHERE THE MAX TIMES PERMITTED ON THE DEVICES AS
 CHOSEN IS LOCATED ON PLANS? (OC TYPE 30MINS) (TIMER
 TYPE 4HRS MAX).
 PLEASE SEE MISSING THE PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.2.ABC.1, TABLES, 415.2.C.1, 415.2.B.1
 PLEASE SHOW A BREAK DOWN ON MAX LIGHTING POWER
 DENSITIES.
  
 ** PREVIOUS REVIEW NOTES**
 PLEASE SEE FBC 2004 CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
 PLEASE SEE SPACE IS IN A BUILDING GREATER THAN 5000 SQ
 FT AND CONTROLS FOR LIGHTING WILL BE REQUIRED (SHOWN),
 HOWEVER PLEASE SEE .1.2, AND .1.3 AS CONTROLS FOR
 SEPARATE SPACES WITH FLR TO CEILING PARTITIONS ARE
 REQUIRED. PLEASE SEE PERMITTED TYPE OF DEVICES AS
 "TIMER" TYPE OVER RIDES ARE ONLY PERMITTED TO OVER RIDE
 NORMAL SCHEDULING A MAX OF 4HRS. PLEASE SEE ANY
 OCCUPANCY SENSOR(S) TYPE DEVICES SHALL ONLY PERMIT A
 MAX OF 30 MINS. PLEASE SHOW LOCATION OF THESE OVER
 RIDES DEVICES AND PLEASE SEE THESE ARE REQUIRED AT THE
 POINT OF ENTRANCE INTO SPACE SO THE OCCUPANT CAN
 VISUALLY SEE LTS BEING CONTROLLED. PLEASE SEE EXCEPTION
 FOR OCC SENSORS. PLEASE SEE BATH R, STOCK RM ETC,,,
 IT IS NOTED BY THIS OFFICE THAT A TIME CLOCK IS BEING
 PROVIDED, HOWEVER PLEASE SEE ABOVE FOR OTHER
 REQUIREMENTS.
  
 3) NOTE: PLEASE SEE NOTE #1, BASED ON THE UNCERTAINTY
 OF LOADS ON THE TRANSFORMER, THE RISER MAY BE NEEDING
 TO BE REVISED AS STATED ON PREVIOUS REVIEWS. THE
 TRANSFORMER WAS CHANGED ONCE TO 75 KVA WHICH WAS OK,
 HOWEVER NOT ALL AREAS OF PLANS WERE REVISED TO
 CORRELATE WITH THIS.
  
 4) NOTE:PLEASE SEE AS NOTED ON PREVIOUS REVIEWS, DO
 NOT USE THE "RUBBER STAMP" WHICH CONTAINS THE WORDING
 OF "CERTIFICATE" FOR SEAL. IT IS NOTED THAT A RAISED
 SEAL IS BEING PLACED OVER THIS RUBBER STAMP.
 THE RUBBER STAMP FOR USE IN THE STATE OF FLORIDA IS NOT
 PERMITTED AND SEEING THAT IT WORDING IS NO LONGER
 VALID, PLEASE DO NOT USE.
 FAC 61G15-23.001, FS 471.025
 AS PREVIOUSLY NOTED.
  
 5) NOTE: PLEASE SEE AS NOTED ABOVE, PLEASE SEE FLORIDA
 STATUTES 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE AS THIS IS ONLY THE 2ND REVIEW UNDER PERMIT
 APPLICATION THE FEE AS MENTIONED IN THE ATTACHED SHEET
 IS NOT ASSESSED, HOWEVER IF PLANS COME BACK WITH ANY OF
 THE ITEMS IN THE NOTES ABOVE NOT ADDRESSED, A 4X FEE IS
 ASSESSED TO THE DESIGN PROFESSIONAL BASED ON THE
 PORTION OF BASE PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
 *** PLEASE KNOW AT THIS TIME, ONE SET OF ME PLANS WILL
 BE RETAINED AND HELD IN FILE FOR POSSIBLE REVIEW BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS AND LEGAL
 COUNSEL TO THE BOARD.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved