| Date |
Text |
| 2006-07-24 00:00:00 | ******* UNSAT ******** |
| | |
| | ** PLEASE KNOW, ALL PLANS ARE REQUIRED |
| | TO HAVE THE STAMPED FROM CITY PLACE ON |
| | ALL SHEETS. PLEASE CONTACT CITY PLACE AT 561-820-0074 |
| | PLEASE DO NOT SUBMIT WITHOUT STAMPS, AS |
| | PLANS MAY BE REJECTED ON THAT ALONE. |
| | |
| | |
| | ** PLEASE KNOW PLANS ARE STILL ONLY |
| | BEING SUBMITTED FOR "PLAN REVIEW" AND |
| | NOT FOR PERMIT. |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS ARE |
| | BASED ON PLANS SUBMITTED FOR THIS REVIEW |
| | ONLY AND PLANS DATED 7/6/06. |
| | |
| | 1) NOTE: PLEASE SEE TITLE SHEET IS |
| | INDICATING A 2004 NATIONAL ELECTRICAL |
| | CODE, HOWEVER PLEASE KNOW, THERE IS NO |
| | 2004 NEC AND PLEASE KNOW AS PER CHAPTER |
| | 27 OF THE 2004 FBC, THE 2002 NEC IS |
| | CURRENTLY IN EFFECT. PLEASE REVISE AND |
| | ADJUST. |
| | |
| | 2) NOTE: PLEASE SEE DESIGNATION BEHIND |
| | RECEPT CIRCUITING ON E 2.0 PLANS SHOW |
| | "E" AND "F" WHICH COULD NOT BE LOCATED |
| | ON SYMBOL LIST/ |
| | PLEASE CLARIFY. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE COLOR CODING FOR |
| | 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| | IT IS UNCLEAR WHERE BLACK AND YELLOW |
| | STRIP COMES FROM? |
| | PLEASE KNOW, AS PER CITY AND PALM BEACH |
| | COUNTY LOCAL AMENDMENTSTHE ABOVE COLOR |
| | CODING HAS BEEN IN EFFECT FOR 25 PLUS |
| | YRS. PLEASE KNOW AS OF THE 2004 FBC |
| | LOCAL TECHNICAL AMENDMENTS DO NOT EXIST, |
| | HOWEVER COLOR CODING FOR CITY OF WEST |
| | PALM BEACH AND PALM BEACH COUNTY SHALL |
| | REMAIN THE SAME AS ALL CURRENT |
| | ELECTRICAL SYSTEMS IN BUILDINGS ARE |
| | CODED PER ABOVE ANDTHE NEC DOES NOT |
| | PROVIDE COLOR CODING FOR 277/480A. |
| | 90.4 |
| | |
| | 4) NOTE: PLEASE PROVIDE LOAD |
| | CALCULATIONS INDICATING LOADS FOR TRACK |
| | LIGHTING PER 220.12B. PLEASE SHOW. |
| | |
| | 5) NOTE: PLEASE INDICATE ALL CONTINUOUS |
| | LOADS AT 125%. 215.3,230.42 ETC. |
| | PLEASE SEE LOADSHOWN ON TRANSFORMER |
| | PLACES LOAD AT 44.97KVA. PLEASE SEE |
| | ABOVE NOTES, AS CONTINUOUS LOADS WILL |
| | PLACE THIS LOAD OVER RATING OF SAID |
| | 45KVA UNIT. |
| | PLEASE CLARIFY WHAT APPEARS TO BE |
| | ADDTIONAL LOAD ON "PA"? HOW, ARE THESE |
| | LOADS DIFFERENT OF THAT ON "DP"? |
| | PLEASE SHOW COMPLETE LOAD CALCULATIONS |
| | PER ABOVE AND 220.3,220.10,220.11,220.13 |
| | ETC. AND 215.3, 230.42 ETC |
| | |
| | 6) NOTE: PLEASE SEE GROUNDING NOTE FOR |
| | TRANSFORMER MENTIONS TO GROUND UNIT TO |
| | EITHER BUILDING STEEL "OR" COLD WATER. |
| | PLEASE SEE 250.50, 250.66 , |
| | 250.20,250.30 AS BOTH WILL BE REQUIRED. |
| | PLEASE NOTE, THIS SHALL BE ATTACHED AND |
| | PART OF THE BUILDINGS GE SYSTEM. |
| | |
| | 7) NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| | 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| | PLEASE SEE SPACE IS IN A BUIDLIGN |
| | GREATER THAN 5000 SQ FT AND CONTROLS FOR |
| | LIGHTING WILL BE REQUIRED (SHOWN), |
| | HOWEVER PLEASE SEE .1.2, AND .1.3 AS |
| | CONTROLS FOR SEPARATE SPACES WITH FLR TO |
| | CEILING PARTITIONS ARE REQUIRED. PLEASE |
| | SEE PERMITTED TYPE OF DEVICES AS "TIMER" |
| | TYPE OVER RIDES ARE ONLY PERMITTED TO |
| | OVER RIDE NORMAL SCHEDULING A MAX OF |
| | 4HRS. PLEASE SEE ANY OCCUPANCY SENSOR(S) |
| | TYPE DEVICES SHALL ONLY PERMIT A MAX OF |
| | 30 MINS. PLEASE SHOW LOCATION OF THESE |
| | OVER RIDES DEVICES AND PLEASE SEE THESE |
| | ARE REQUIRED AT THE POINT OF ENTRANCE |
| | INTO SPACE SO THE OCCUPANT CAN VISUALLY |
| | SEE LTS BEING CONTROLLED. PLEASE SEE |
| | EXCEPTION FOR OCC SENSORS. |
| | PLEASE SEE BATH R, STOCK RM ETC,,, |
| | IT IS NOTED BY THIS OFFICE THAT A TIME |
| | CLOCK IS BEING PROIVIDED , HOWEVER |
| | PLEASE SEE ABOVE FOR OTHER REQUIREMENTS. |
| | |
| | 8) NOTE: PLEASE SEE NOTES SHOW #8 FOR |
| | FEED TO TRANSFORMER, HOWEVER A 60A BRKR |
| | IS SHOWN. PLEASE SEE 310.16, 240.4, |
| | 110.14, AS THE MEX OCP FOR THE #8' IS |
| | 50A'S. PLEASE SEE 310.16 75 DEGREE |
| | COLUMN AS THE #8'S ARE RATED AT 50A'S. |
| | PLEASE ADJUST ONCE ALL CALCULATIONS ARE |
| | DONE. |
| | |
| | |
| | ** IMPORTANT** |
| | |
| | PLEASE SURE WHEN RESUBMITTING PLANS TO |
| | COMPLETELY REMOVE ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE ONLY SUBMIT ONE SET OF |
| | THE OLD/VOIDED SHEETS FOR REFERENCE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |