Plan Review Notes
Plan Review Notes For Permit 06050449
Permit Number 06050449
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-21 00:00:00 
 NONCOMPLIANT
  
  
 1} PLEASE SEE THE EMERGENCY LIGHTS MUST
 BE ON THE SAME CIRCUITS RTHE LIGHTING
 IN THE AREA PER 700.12(E), 2002 NEC.
  
 "THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES."
  
 THE EXCEPTION DOES NOT APPLY, THERE IS
 ONLY ONE CIRCUIT IN THE STORAGE ROOM.
  
 2} THE NOTE REGARDING THE 2005 CODE,
 "REVIEW COMMENTS", SHOULD BE CHANGED TO
 READ 2002 NEC, THE CURRENT NEC FOR THE
 STATE OF FLORIDA.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  