| Plan Review Notes For Permit 06050449 |
| Permit Number |
06050449 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-21 00:00:00 | | | | NONCOMPLIANT | | | | | | | | | 1} PLEASE SEE THE EMERGENCY LIGHTS MUST | | | BE ON THE SAME CIRCUITS RTHE LIGHTING | | | IN THE AREA PER 700.12(E), 2002 NEC. | | | | | | "THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES." | | | | | | THE EXCEPTION DOES NOT APPLY, THERE IS | | | ONLY ONE CIRCUIT IN THE STORAGE ROOM. | | | | | | 2} THE NOTE REGARDING THE 2005 CODE, | | | "REVIEW COMMENTS", SHOULD BE CHANGED TO | | | READ 2002 NEC, THE CURRENT NEC FOR THE | | | STATE OF FLORIDA. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|