| Plan Review Notes For Permit 06050448 |
| Permit Number |
06050448 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-01 00:00:00 | DENIED: | | | | | | 1.PER NFPA 110 CHAPTER 7 INSTALLATION | | | OF EMERGENCY POWER SYSTEMS, SUB-SECTION | | | 7.4.1.1 & MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS, A RAISED FOUNDATION OR | | | SLAB OF 6 INCHES OR MORE ABOVE FLOOR | | | LEVEL WILL MAKE SERVICING EASIER. | | | | | | 2.MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS INDICATE A MINIMUM OF 3 | | | FEET CLEARANCE ON ALL SIDES OF THE | | | GENERATOR SET.PLEASE INDICATE ON THE | | | PLAN CLEARANCE AROUND THE GENERATOR. | | | | | | 3.THE MANUFACTURE SUBMITTAL & THE | | | CONSTRUCTION PLANS INDICATE A 500 GALLON | | | SUB-BASE FUEL TANK BUT THE ELECTRICAL | | | SITE PLANS BY SMITH ENGINEERING | | | CONSULTANTS, INC. INDICATE 100 GALLON | | | SUB-BASE FUEL TANK. | | | | | | 4.PLEASE INDICATE IF THIS WILL HAVE A | | | REMOTE FILL.PLEASE INDICATE FUEL | | | SERVICE AND ACCESS FOR FILL PIPING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6179 OR | | | E-MAIL [email protected]. |
|