| Date |
Text |
| 2006-05-16 00:00:00 | ******** UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS FOR GENERATOR, ATS , |
| | MTS AND SUB BASE FUEL TANK. |
| | PLEASE KNOW, ALL MUST INDICATE LISTING |
| | FROM A NRTL. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE CORRELATE PLANS |
| | SUBMITTED. PLEASE SEE ONE SET INDICATES |
| | A 100 GAL TANK, AND THE OTHER 500 GAL |
| | TANK?? |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHALL |
| | REFERENCE THE CURRENT CODES IN EFFECT |
| | AS, THE "LATEST EDITION" MAY NOT BE |
| | ADOPTED AT THIS TIME. |
| | WORK, PER 2002 NFPA-70, 2002 NFPA-110 |
| | 2004 FBC. |
| | |
| | 4) NOTE: PLEASE CLARIFY FEED TO THE 250A |
| | DISC FOR MTS SHOWING 3- 200A RECEPTS?? |
| | THE THREE RECEPTS ARE UNCLEAR. PLEASE |
| | ALSO SEE ALL DISCONNECTS, MAINS ETC ARE |
| | SHOWN AS 250A'S, YET THESE RECEPTS ARE |
| | SHOWN AS 200A'S? |
| | PLEASE SEE THE LOADS SHOWN SEEM TO BE |
| | OVER THE RATINGS OF THE 200A RECEPT? |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE VERIFY TAPPED CONDUCTORS |
| | AS SHOWN PER 240.21, LENGTH? |
| | PLEASE SEE 450.3 FOR MAX OCP AT 125%. |
| | WHEN THE OCP DOES NOT CORRELATE, IT IS |
| | PERMITTED TO GO TO THE NEXT STANDARD |
| | SIZE PER 240.6. (25A'S). |
| | SHOWS 40A'S. |
| | |
| | 6) NOTE: PLEASE SEE THE MTS MUST CONTAIN |
| | A "OFF" POSITION AS THE MEANS OF |
| | DISCONNECT REQUIRED FOR POWER COMING |
| | FROM THE GEN. THE BRKR ON THE INSIDE OF |
| | THE GEN CAN NOT BE THE DISCONNECT MEANS |
| | FOR POWER IN EM CONDITIONS. |
| | 225.31-225.39. |
| | |
| | 7) NOTE: PLEASE SEE BLDG REVIEW, AS THE |
| | WIND LOAD CALCUALTIONS ARE REQUIRED AT |
| | THIS TIME FOR NEW LT POLE(S). |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY COMMENTS OR |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |